| 2021-09-30 23:47:44 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NO MAINS SHOWN AT SERVICE. SERVICE MAINS MUST BE |
| | GROUPED. NEC 230.72 |
| | |
| | 2. SERVICE ENTRANCE CONDUCTORS SIZE ARE INSUFFICIENT |
| | FOR SERVICE SIZE. CALCULATED LOAD SHOWN TO BE 256AMPS. |
| | 4/0 WIRE SHOWN IS ONLY PERMISSIBLE FOR 230AMPS AT |
| | 75DEGREES CELCIUS. MINIMUM 250MCM REQUIRED. NEC 230.23A |
| | |
| | 3. EQUIPMENT GROUNDING CONDUCTOR SHOWN FROM METER CANS |
| | TO 1ST MEANS OF DISCONNECTS. THIS IS NOT PERMITTED AND |
| | PROVIDED A PARALLEL PATH BACK TO THE GROUNDED |
| | CONDUCTOR. EQUIPMENT GROUND ORIGINATES AFTER 1ST MEANS |
| | OF DISCONNECT. PROVIDE CORRECTION. NEC 250.24C |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-805-6744 |
| | |