Plan Review Notes
Plan Review Notes For Permit 21071231
Permit Number 21071231
Review Stop E
Sequence Number 2
Notes
Date Text
2021-09-30 23:47:44ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO MAINS SHOWN AT SERVICE. SERVICE MAINS MUST BE
 GROUPED. NEC 230.72
  
 2. SERVICE ENTRANCE CONDUCTORS SIZE ARE INSUFFICIENT
 FOR SERVICE SIZE. CALCULATED LOAD SHOWN TO BE 256AMPS.
 4/0 WIRE SHOWN IS ONLY PERMISSIBLE FOR 230AMPS AT
 75DEGREES CELCIUS. MINIMUM 250MCM REQUIRED. NEC 230.23A
  
 3. EQUIPMENT GROUNDING CONDUCTOR SHOWN FROM METER CANS
 TO 1ST MEANS OF DISCONNECTS. THIS IS NOT PERMITTED AND
 PROVIDED A PARALLEL PATH BACK TO THE GROUNDED
 CONDUCTOR. EQUIPMENT GROUND ORIGINATES AFTER 1ST MEANS
 OF DISCONNECT. PROVIDE CORRECTION. NEC 250.24C
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved