2021-09-23 11:13:01REBUILD DUPLEX (R3) SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21071231
  
 ORIGINAL COMMENT:
 1- PERMIT APPLICATION STATES: "REMODEL TWO STORY
 BUILDING AS PER PLANS". PLANS SUBMITTED ARE FOR
 COMPLETE CONSTRUCTION OF A TWO STORY DUPLEX. NEED TO
 REVISE THE SCOPE OF WORK ON THE PERMIT APPLICATION TO
 SAY CONSTRUCTION OF A NEW TWO STORY DUPLEX.
 THE PERMIT TYPE WILL BE CHANGED FROM RESIDENTIAL
 REMODEL TO NEW RESIDENTIAL BUILDING PERMIT. SEC.
 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 BASED ON REVISED PLANS SUBMITTED, THE SCOPE OF WORK IS
 TO REBUILT THE TWO STORY DUPLEX. PERMIT TYPE WAS
 CHANGED TO BUILDING-RESIDENTIAL PERMIT. SEC. 107.2.1
 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 2- BASED ON ITEM #1 ABOVE. VALUATION DECLARED IN THE
 PERMIT APPLICATION IS TOO LOW. VALUATION TO INCLUDE ALL
 LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT AND
 DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS.
 VALUATION WAS UPDATED TO $182843.00. OWES $2250.65.
  
 RESPONSE:
 FEES NEED TO BE PAID WHEN PERMIT IS APPROVED.
  
 ORIGINAL COMMENT:
 3- NEED TO APPLY FOR A SEPARATE BUILDING DEMOLITION
 PERMIT IN ORDER TO DEMOLISH OLD BUILDING. SEC. 105.1
 CITY AMENDMENTS.
  
 RESPONSE:
 WILL NEED DEMOLITION PERMIT.
  
 ORIGINAL COMMENT:
 4- NEED TO SPECIFY A LISTED FIRE RATED CEILING /FLOOR
 ASSEMBLY TESTED IN ACCORDANCE WITH ASTM E119 OR UL263
 AS REQUIRED BY SEC. R302.3 FBC-RESIDENTIAL.
  
 RESPONSE:
 1 HOUR FIRE RATED FLOOR/CEILING ASSEMBLY DETAIL SHOWN
 ON SHEET 2-4 IS INCORRECT. UL DESIGN U465 IS FOR WALL
 ASSEMBLIES NOT FOR FLOOR/CEILING ASSEMBLIES. REVISE AS
 REQUIRED. NEED TO SPECIFY AN APPROVED FLOOR /CEILING
 ASSEMBLY.
 ALSO, INFORMATION SHOWN ON THE 1 HOUR FIRE RATED
 FLOOR/CEILING ASSEMBLY DETAIL DOESN'T MATCH INFORMATION
 SHOWN ON THE TYPICAL WALL SECTION ON SAME SHEET 2-4.
 REVISE AS REQUIRED AND COORDINATE ACCORDINGLY WITH
 CORRECT FLOOR/CEILING ASSEMBLY DETAIL.
  
 ORIGINAL COMMENT:
 5- NEED TO PROVIDE FIRE RATED PENETRATIONS DETAILS AND
 SPECIFICATIONS FOR THE FIRE RATED FLOOR CEILING
 ASSEMBLY AS REQUIRED BY SEC. R302.4 FBC-RESIDENTIAL.
  
 RESPONSE:
 ENGINEER'S RESPONSE LETTER STATES "INFORMATION HAS BENN
 UPDATED ON SHEET 2-4". INFORMATION WAS NOT PROVIDED.
  
 6- OK.
  
 ORIGINAL COMMENT:
 7- LOT DRAINAGE
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 RESPONSE:
 ENGINEER'S RESPONSE LETTER STATES "THIS IS A REMODEL
 PROJECT". THIS IS INCORRECT. BASED ON PLANS SUBMITTED
 SOIL IS ALTERED FOR PROPOSED CONSTRUCTION. PROVIDE
 REQUIRED DRAINAGE PLAN.
 NOTE: NORTH SIDE OF RECONSTRUCTED BUILDING IS TOO CLOSE
 TO THE THE ADJACENT PROPERTY. TAKE THIS INTO
 CONSIDERATION WHEN DOING THE DRAINAGE PLAN. WATER CAN
 NOT BE DIVERTED TO ADJACENT PROPERTIES.
  
 8- ACCORDING TO SURVEY SUBMITTED THE NORTH WALL OF
 BUILDING IS LOCATED LESS THAN 3 FEET FROM THE PROPERTY
 LINE. THE FOLLOWING FIRE RESISTANT CONSTRUCTION IS
 REQUIRED:
  
 ORIGINAL COMMENT:
 A) PROJECTIONS: NEED TO SPECIFY 1 HOUR FIRE RATED
 ASSEMBLY ON THE UNDERSIDE OF THE ROOF PROJECTION. TABLE
 R302.1 FBC-RESIDENTIAL.
 NOTE: TAKE INTO CONSIDERATION OPENINGS FOR ATTIC
 VENTILATION.
  
 RESPONSE:
 THERE IS NO DETAIL FOR 1 HOUR FIRE RATED ASSEMBLY ON
 THE UNDERSIDE OF THE ROOF PROJECTION.
 ALSO, THERE IS NO INFORMATION ABOUT THE ATTIC VENTS ON
 THE NORTH SIDE OF THE BUILDING.
 TYPICAL WALL SECTION ON SHEET 2-4 SPECIFIES VENTS @
 8'-0" O.C. VENTS ARE NOT ALLOWED ON THE NORTH SIDE OF
 THE BUILDING. ENGINEER OF RECORD TO SHOW ON THE ROOF
 PLAN HOW PROVIDING THE CROSS VENTILATION AT THE 1/150
 RATIO AS REQUIRED BY SEC. R806.1 AND SEC. R806.2
 FBC-RESIDENTIAL. PROVIDE CALCULATIONS FOR THE REQUIRED
 NUMBER OF VENTS.
  
 B)OK.
  
 ORIGINAL COMMENT:
 C)PROVIDE FIRE RATED DETAIL/SPECIFICATIONS FOR ANY WALL
 PENETRATIONS. TABLE R302.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. SEE ELECTRICAL PLAN FOR
 WALL PENETRATIONS.
  
 9- STAIRWAY CONSTRUCTION:
 A)
  
 ORIGINAL COMMENT:
 B)PROVIDE NOSING DETAIL/SPECIFICATIONS AS REQUIRED BY
 SEC. R311.7.5.3 FBC-RESIDENTIAL.
  
 RESPONSE:
 STAIR DETAIL ON SHEET 3-4 SHOWS 1/2" NOSING PROJECTION.
 NEED A NOSING PROJECTION NOT LESS THAN 3/4". REVISE AS
 REQUIRED.
 NOTE: STAIR DETAIL SHOWS MARBLE TREADS AND RISERS.
 THESE ARE EXTERIOR STAIRS. THERE IS A CONCERN ABOUT
 THESE STAIRS BEING TOO SLIPPERY WHEN WET. PROVIDE
 DETAIL/SPECIFICATIONS SHOWING HOW TO AVOID SLIPPERY
 TREADS. SEC. 101.3 CITY AMENDMENTS.
  
 C) OK.
 D) OK.
  
 E) AFTER THE PERMIT IS ISSUED NEED TO SUBMIT HANDRAIL
 AND GUARDRAIL SHOP DRAWINGS APPROVED BY ENGINEER OF
 RECORD AS DEFERRED SUBMITTAL. SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 10- OK
 11- OK.
 12-OK.
 13-OK
  
 14- ENERGY CALCULATIONS SUBMITTED:
 A) OK
  
 ORIGINAL COMMENT:
 B)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. CORRECT ADDRESS IS 929 SELKIRK ST. NOT 923.
 PROVIDE OWNER AND BUILDER INFORMATION. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 DOWNSTAIR & UPSTAIR UNITS ASSIGNED ADDRESS ARE OK ON
 EACH ENERGY CALCULATIONS SUBMITTED. REQUESTED OWNER AND
 BUILDER INFORMATION WAS NOT PROVIDED. NEED TO PROVIDE
 THIS INFORMATION.
  
 C)OK.
 D) OK
 E) OK
 F) OK
 G) OK
 H) OK
 I) OK
 J)OK
 K)OK
  
 ORIGINAL COMMENT:
 L)PROVIDE CORRECT INFORMATION FOR "WINDOWS" INFORMATION
 ON PAGE 3. THERE ARE TWO UNITS. WINDOW OVERHEAD
 SEPARATION VARIES FROM FIRST FLOOR UNIT TO SECOND FLOOR
 UNIT. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 WINDOW OVERHEAD SEPARATION FOR DOWNSTAIR UNIT (927
 SELKIRK ST) IS INCORRECT. SEE BUILDING ELEVATIONS AND
 REVISE AS REQUIRED.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]