Plan Review Notes
Plan Review Notes For Permit 21071231
Permit Number 21071231
Review Stop B
Sequence Number 1
Notes
Date Text
2021-08-20 11:23:03DUPLEX (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21071231
  
 1- PERMIT APPLICATION STATES: "REMODEL TWO STORY
 BUILDING AS PER PLANS". PLANS SUBMITTED ARE FOR
 COMPLETE CONSTRUCTION OF A TWO STORY DUPLEX. NEED TO
 REVISE THE SCOPE OF WORK ON THE PERMIT APPLICATION TO
 SAY CONSTRUCTION OF A NEW TWO STORY DUPLEX.
 THE PERMIT TYPE WILL BE CHANGED FROM RESIDENTIAL
 REMODEL TO NEW RESIDENTIAL BUILDING PERMIT. SEC.
 107.2.1 CITY AMENDMENTS.
  
 2- BASED ON ITEM #1 ABOVE. VALUATION DECLARED IN THE
 PERMIT APPLICATION IS TOO LOW. VALUATION TO INCLUDE ALL
 LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT AND
 DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS.
 VALUATION WAS UPDATED TO $182843.00. OWES $2250.65.
  
 3- NEED TO APPLY FOR A SEPARATE BUILDING DEMOLITION
 PERMIT IN ORDER TO DEMOLISH OLD BUILDING. SEC. 105.1
 CITY AMENDMENTS.
  
 4- NEED TO SPECIFY A LISTED FIRE RATED CEILING /FLOOR
 ASSEMBLY TESTED IN ACCORDANCE WITH ASTM E119 OR UL263
 AS REQUIRED BY SEC. R302.3 FBC-RESIDENTIAL.
  
 5- NEED TO PROVIDE FIRE RATED PENETRATIONS DETAILS AND
 SPECIFICATIONS FOR THE FIRE RATED FLOOR CEILING
 ASSEMBLY AS REQUIRED BY SEC. R302.4 FBC-RESIDENTIAL.
  
 6- NEED TO PROVIDE DETAILS AND SPECIFICATIONS FOR THE
 INSTALLATION OF THE A/C DUCTWORK FOR THE FIRST FLOOR
 DWELLING UNIT. IS THERE A DROPPED CEILING?
 SEC. R302.4 FBC-RESIDENTIAL.
  
 7- LOT DRAINAGE
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 8- ACCORDING TO SURVEY SUBMITTED THE NORTH WALL OF
 BUILDING IS LOCATED LESS THAN 3 FEET FROM THE PROPERTY
 LINE. THE FOLLOWING FIRE RESISTANT CONSTRUCTION IS
 REQUIRED:
 A) PROJECTIONS: NEED TO SPECIFY 1 HOUR FIRE RATED
 ASSEMBLY ON THE UNDERSIDE OF THE ROOF PROJECTION. TABLE
 R302.1 FBC-RESIDENTIAL.
 NOTE: TAKE INTO CONSIDERATION OPENINGS FOR ATTIC
 VENTILATION.
  
 B)WINDOWS ARE NOT ALLOWED. TABLE R302.1
 FBC-RESIDENTIAL.
  
 C)PROVIDE FIRE RATED DETAIL/SPECIFICATIONS FOR ANY WALL
 PENETRATIONS. TABLE R302.1 FBC-RESIDENTIAL.
  
 9- STAIRWAY CONSTRUCTION:
 A)CONCRETE STAIR SECTION ON SHEET 3-4: NUMBER OF TREADS
 AND RISERS SPECIFIED DON'T MATCH NUMBER OF TREADS AND
 RISER SHOWN ON THE DETAIL. REVISE AS REQUIRED TO MATCH.
 NOTE: SAME COMMENT APPLIES TO STAIRS SHOWN ON FIRST
 FLOOR PLAN VIEW ON SHEET 1-4.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 B)PROVIDE NOSING DETAIL/SPECIFICATIONS AS REQUIRED BY
 SEC. R311.7.5.3 FBC-RESIDENTIAL.
  
 C)TYPICAL STAIR & GUARDRAIL NOTES SPECIFIED ON SHEET
 3-4. THE BALUSTERS REQUIRED RESISTANCE IS NOT 25LB PER
 SQUARE FOOT. SEE TABLE R301.5 FBC-RESIDENTIAL AND
 REVISE AS REQUIRED.
 ALSO, ALL THE NOTES NEED TO REFERENCE THE CORRECT CODE
 SECTION FROM THE FBC-RESIDENTIAL CODE NOT THE
 FBC-BUILDING. REVISE AS REQUIRED.
  
 D) CONCRETE STAIR SECTION ON SHEET 3-4: REVISE HANDRAIL
 NOTE STATING "34-38" HANDRAIL BY OTHERS". THIS HANDRAIL
 IS A GUARDRAIL AND THE MINIMUM HEIGHT IS 36". SEE SEC.
 R312.1.2 FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 E) NEED TO SUBMIT HANDRAIL AND GUARDRAIL SHOP DRAWINGS
 APPROVED BY ENGINEER OF RECORD AS DEFERRED SUBMITTAL.
 SEC. 107.3.4.1 CITY AMENDMENTS.
  
 10- PROPOSED FLOOR PLANS AND SURVEY SUBMITTED DON'T
 MATCH.
 REVISE AS REQUIRED TO MATCH. SEE DIMENSIONS AND
 STAIRWAY.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 11- PROVIDE COMPLETE DETAIL/SPECIFICATIONS FOR CANOPY
 ABOVE FIRST FLOOR ENTRY DOOR. CLEARLY SPECIFY ALL
 FRAMING MEMBERS AND CONNECTORS. SEC. R301.1
 FBC-RESIDENTIAL.
 NOTE: IT LOOKS LIKE THIS DETAIL IS ON SHEET 2-4 BUT IT
 IS NOT LABELED AND NEED TO BE REVISED. SIMPSON MP24
 MENDING PLATE IS NOT AN STRUCTURAL CONNECTOR (SEE
 SIMPSON CATALOG). SIZE OF STEEL ANGLE CONNECTING THE
 CANOPY TO THE WALL IS NOT SPECIFIED. PROVIDE COMPLETE
 INFORMATION FOR THE SHEATHING, ROOFING , UNDERLAYMENT,
 ETC. MOST LIKELY THERE ARE NOT TRUSSES FOR THIS LITTLE
 CANOPY (REVISE AS REQUIRED OR PROVIDE TRUSS PACKAGE
 SHOWING THIS LITTLE ROOF AREA).
  
 12- SHEET 4-4:
 A)PLYWOOD ROOD SHEATHING NOTE ON THE GENERAL ROOF NOTES
 AND NOTE BELOW THE COMPONENT AND CLADDING PRESSURES
 ZONES TABLE DON'T MATCH THOSE SHOWN ON THE COMPONENT
 AND CLADDING PRESSURES ZONES TABLE. REVISE AS REQUIRED
 TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 13- FIRST FLOOR BATHROOM NEEDS A DOOR THAT PROVIDE 29"
 MIN. CLEAR OPENING. SPECIFIED 30" DOOR DOESN'T COMPLY.
 SEC. R320.1 FBC-RESIDENTIAL.
  
 14- ENERGY CALCULATIONS SUBMITTED:
 NOTE: ENERGY CALCULATIONS SUBMITTED ARE SEPARATE FOR
 EACH DWELLING UNIT. COMMENTS BELOW APPLY TO BOTH
 CALCULATIONS SUBMITTED. COORDINATE AND REVISE
 ACCORDINGLY.
  
 A)ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED
 AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. CORRECT ADDRESS IS 929 SELKIRK ST. NOT 923.
 PROVIDE OWNER AND BUILDER INFORMATION. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C)PROVIDE CORRECT INFORMATION FOR ITEM #2. THE QUESTION
 ON THIS ITEM IS SINGLE FAMILY OR MULTIPLE FAMILY?.
 "DETACHED IS NOT THE ANSWER. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D)PROVIDE CORRECT INFORMATION FOR ITEM #3. THERE ARE
 TWO UNITS.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 E)PROVIDE CORRECT INFORMATION FOR ITEM #6. NEED TO
 PROVIDE THE A/C AREA FOR EACH UNIT, NOT ENTIRE
 BUILDING. SEE PLANS A/C AREA OF EACH UNIT. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F)PROVIDE CORRECT INFORMATION FOR ITEM #9. THERE ARE
 TWO UNITS. ONE IS ON SLAB ON GRADE AND THE OTHER ONE IS
 NOT. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G)PROVIDE CORRECT INFORMATION FOR ITEM #11. NOTE: THERE
 ARE TWO UNITS. THIS INFORMATION VARIES FOR EACH UNIT.
 ALSO, SEE PLANS FOR CORRECT INSULATION R-VALUE AND
 VENTILATION. TOP UNIT IS VENTED.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 H)PROVIDE CORRECT INFORMATION FOR "BLOCKS" INFORMATION
 ON PAGE 2. THERE ARE TWO UNITS, NOT ENTIRE HOUSE.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 I)PROVIDE CORRECT INFORMATION FOR "SPACES" INFORMATION
 ON PAGE 2. THERE ARE TWO UNITS, NOT ENTIRE HOUSE.
 REVISE NUMBER OF OCCUPANTS AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 NOTE: TYPICALLY, THE NUMBER OF OCCUPANTS IS BASED ON
 THE NUMBER OF BEDROOMS. NUMBER OF PEOPLE IS NOT ADDED
 FOR THE LIVING ROOM AND BEDROOM.
  
 J)PROVIDE CORRECT INFORMATION FOR "FLOORS" INFORMATION
 ON PAGE 2. THERE ARE TWO UNITS. ONE IS ON SLAB ON GRADE
 AND THE OTHER ONE IS NOT. SEE PLANS AND REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 K)PROVIDE CORRECT INFORMATION FOR "DOORS" INFORMATION
 ON PAGE 3. THERE ARE TWO UNITS. DOOR ORIENTATION IS
 DIFFERENT. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 L)PROVIDE CORRECT INFORMATION FOR "WINDOWS" INFORMATION
 ON PAGE 3. THERE ARE TWO UNITS. WINDOW OVERHEAD
 SEPARATION VARIES FROM FIRST FLOOR UNIT TO SECOND FLOOR
 UNIT. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 M)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712