| 2021-08-10 14:17:20 | CONDO REMODEL |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) THE TEST REPORTS PROVIDED INCLUDE A DROP CEILING AS |
| | PART OF THE ASSEMBLY THAT WAS TESTED - MOST UNITS DO |
| | NOT HAVE A DROP CEILING WITH INSULATION - PLEASE |
| | PROVIDE TEST REPORTS THAT INCLUDE ONLY THE CONCRETE |
| | SLAB, UNDERLAYMENT AND THE TILE - |
| | |
| | THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED: |
| | |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.. |
| | PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | 2). YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO |
| | VERIFY THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING |
| | TO PROJECTDOX ( [email protected] ) |
| | |