| 2021-09-01 13:08:46 | 09/01/21 2ND LP GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. SIGNED AND SEALED DRAWINGS NEED TO BE |
| | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR - |
| | IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL |
| | SIGNATURE - PLEASE DROP OFF THE ORIGINAL SIGNED AND |
| | SEALED DOCUMENT ALONG WITH A "PLAN REVIEW REQUEST FORM" |
| | EXPLAINING THE REASON FOR SUBMITTING THE DOCUMENT OR |
| | DRAWINGS. THE PLAN REVIEW REQUEST FORM CAN BE OBTAINED |
| | BY EMAILING [email protected] AND ASKING FOR THE FORM. |
| | |
| | 2. WOULD YOU PLEASE SUBMIT THE CORRECT BTU LOAD ON THE |
| | SYSTEM. THE 355 BTU'S IS INCORRECT, AND THIS MAY BE |
| | REDLINED IF PERMISSION IS GIVEN PER THE WPB AMENDMENTS |
| | TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 3. SHOW THE DEPTH OF THE LP GAS CONTAINER BELOW GRADE |
| | TO COMPLY WITH NFPA 58 SEC. 6.6.6.1. |
| | |
| | 4. THE COPY OF THE TIE-DOWN IS NOT ACCEPTABLE. THE |
| | ENGINEER WHO PREPARED THE TANK TIE-DOWN DETAILS SHALL |
| | PROVIDE AN ELECTRONIC SIGNATURE AND SEAL THE DOCUMENT- |
| | FL. STATUTE 471.025 & FLORIDA ADMINISTRATIVE CODE SEC. |
| | 61G15-23.005. VISIT HTTPS://WWW.ENGINEERINGEXPRESS.COM/ |
| | THEY MAY BE ABLE TO PROVIDE THIS DOCUMENT. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |