Plan Review Notes
Plan Review Notes For Permit 21071168
Permit Number 21071168
Review Stop B
Sequence Number 2
Notes
Date Text
2021-11-01 10:32:10WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21071168
 ADD: 5600 N FLAGLER DR. # 1505
 CONT: NR WINDOWS
 TEL: 561-844-1121
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. NOV. 01ST/ 2021
 ACTION: DENIED
  
 1) 2ND REQUEST IT APPEARS PAPER STAMPED (ENGINEERS SEAL
 AND SIGNATURE) SHEETS WERE PAPER WITH SEAL AND
 SIGNATURE THEN UPLOADED. FLORIDA ADMINISTRATIVE CODE
 61G15-23.005 (3)(C) A DOCUMENT IN THE FILE FOLDER,
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 DIGITALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2) 2ND REQUEST. LAST WEEK I CONTACTED NR WINDOWS ABOUT
 THIS ISSUE BUT NOTHING EVER HAPPENED. THE DESIGN
 PRESSURES BY YOUR ENGINEER FOR THE SINGLE HUNG WINDOW
 ARE GIVEN AS +/- 71.7 PSF VASD (FL 20352.1) ENGINEERS
 SHEET 2OF 2. THE SUBMITTED SINGLE HUNG WINDOW APPROVAL
 IS FL 22250-R4, PAGE 1 OF 10 TECHNICAL SHEETS GLAZING
 TYPE 1 IS CIRCLED. PAGE 2 OF 10 EQUAL LITES CIRCLED AND
 GLASS TYPE 1 CIRCLED. THIS TYPE FRAME, STANDARD SILL IS
 GOOD FOR +60/ -80 PSF VASD. WHAT I CALLED LAST WEEK
 ABOUT IS THE HI-RISE SILL WITH GLASS TYPE 1 IS GOOD FOR
 BOTH +/- 80 PSF VASD, OF THE 4 SYSTEMS THIS IS THE ONLY
 ONE THAT MEETS BOTH THE POSITIVE AND NEGATIVE
 PRESSURES.
  
 1ST ROUND OF COMMENTS. PLEASE IDENTIFY IN THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, SILL HEIGTH, TYPE OF GLAZING, MULLION
 SIZE, LENGTH IF UNREINFORCED OR REINFORCED INFORMATION
 IF REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR
 EACH OPENING SIZE. 2020 FBC-B 1405.13.1 INSTALLATION.
 WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH
 APPROVED MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND
 SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND
 SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING
 USED IN THE TESTS.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  