| 2021-08-10 16:42:44 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21071167 2471 OKEECHOBEE BLVD #A |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | 1.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC |
| | CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS |
| | FOR NEW TOILET ROOM INDICATING THE FOLLOWING: |
| | ?.A)PROVIDE DETAIL FOR ACCESSIBLE LAVATORIES. |
| | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC |
| | 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS |
| | REQUIRED BY FBC ACC 306.2 AND 306.3 |
| | ?.B)PROVIDE LOCATIONS AND DETAIL FOR ACCESSIBLE |
| | MIRRORS. MIRRORS LOCATED ABOVE LAVATORIES OR |
| | COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF |
| | THE REFLECTING SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE |
| | THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE |
| | LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE |
| | BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890 |
| | MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC |
| | ACC 603.3. |
| | ?.C)PROVIDE DIMENSIONED FLOOR PLAN OF AFFECTED PUBLIC |
| | RESTROOMS. PER FBC ACC 602.2 SHOW ALL REQUIRED CLEAR |
| | FLOOR SPACES COMPLYING WITH 305 AND TURNING SPACES |
| | COMPLYING WITH 304.3.1 OR 304.3.2. |
| | |
| | 2.RE: PLAN SHEET CS1-0; INDEX OF DRAWINGS DOES NOT LIST |
| | SUBMITTED PLAN SHEETS E0.0 LEGENDS & KEYNOTES AND MP1.0 |
| | MECH & PLUMBING. PER WPB FBC 107.2, REVISE TO REFLECT. |
| | |
| | 3.ARCHITECTURAL INDICATE PUBLIC RESTROOMS AND SINGLE |
| | USE RESTROOM ARE NOT IN THE SCOPE OF WORK/CONTRACT AND |
| | DEMO PLANS SEEM TO INDICATE THE SAME. MP1.0 AND |
| | ELECTRICAL DRAWINGS INDICATE THE PUBLIC RESTROOMS ARE |
| | IN THE SCOPE OF WORK/CONTRACT. ELECTRICAL DRAWINGS ALSO |
| | INDICATE THE SINGLE USE RESTROOM IS IN THE SCOPE OF |
| | WORK/CONTRACT; MP1.0 DOES NOT. PER WPB FBC 107.2.1, |
| | CLARIFY. |
| | |
| | 4.PER WPB FBC 107.2.1, SHOW EXISTING DRINKING FOUNTAIN |
| | WITH DESCRIPTION OF THE SAME (I.E. BI-LEVEL ADA |
| | COMPLIANT). |
| | |
| | 5. MP1.0 PLUMBING PLAN NOTE 1 INDICATES BUT DOES NOT |
| | DIRECTLY STATE THAT MODIFICATION OF IN-WALL PLUMBING |
| | MAY BE REQUIRED TO REPLACE EXISTING PLUMBING FIXTURES |
| | WITH THE NEW FIXTURES. IT IS ASSUMED THAT THIS WOULD BE |
| | CAUSED BY CHANGED ROUGH IN ELEVATIONS OR MINOR OFF-SETS |
| | WITH-OUT CHANGE TO THE ORIGINAL PIPING INTENT (I.E., |
| | ADDING, DELETING VENTS, FIXTURE BRANCHES, ETC.) IF THIS |
| | IS THE CASE, NEW PLUMBING PIPING PLAN VIEW AND RISER |
| | DIAGRAMS ARE NOT REQUIRED. HOWEVER, AN IN-WALL ROUGH-IN |
| | INSPECTION WILL BE REQUIRED. PER WPB FBC 107.2.1, |
| | CONFIRM THE INTENT OF THE NOTE. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |
| | 21071167 2471 OKEECHOBEE BLVD #A |
| | |
| | |
| | |