Plan Review Notes
Plan Review Notes For Permit 21071166
Permit Number 21071166
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-07-23 15:37:16THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE CITY UTILITY DEPT. REQUIRES A SEPARATE METER FOR
 THE FIRE SPRINKLER SYSTEM.
  
 PLEASE REVIEW, CONTACT THEM AND ARRANGE FOR APPLICABLE
 REQUIREMENTS.
  
  
 2) THE FIRE LINE UNDER GROUNDING WORK SHALL BE DONE
 UNDER A SEPARATE PERMIT WITH SPECIFIC DETAILS AND
 PRODUCT SUBMITTALS.
  
 PER NFPA 13D
  
 5.3* UNDERGROUND PIPE. ANY TYPE OF PIPE OR TUBE
 ACCEPTABLE
 UNDER THE APPLICABLE PLUMBING CODE FOR UNDERGROUND
 SUPPLY
 PIPE SHALL BE ACCEPTABLE AS AN UNDERGROUND SUPPLY FOR A
 FIRE
 SPRINKLER SYSTEM WHEN INSTALLED BETWEEN THE POINT OF
 CONNECTION
 AND THE SYSTEM RISER.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND DETAILS
  
  
  
 3) THERE IS NO INDICATIONS OF A DDCV. THE PER UTILITY
 DEPT. THE FIRE SHALL SHALL HAVE IT'S OWN DDCV TO
 PROTECT THE WATER SUPPLY.
  
 PLEASE REVIEW, CONTACT THEM AND ARRANGE FOR APPLICABLE
 REQUIREMENTS.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  