| 2021-07-23 15:37:16 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE CITY UTILITY DEPT. REQUIRES A SEPARATE METER FOR | | | THE FIRE SPRINKLER SYSTEM. | | | | | | PLEASE REVIEW, CONTACT THEM AND ARRANGE FOR APPLICABLE | | | REQUIREMENTS. | | | | | | | | | 2) THE FIRE LINE UNDER GROUNDING WORK SHALL BE DONE | | | UNDER A SEPARATE PERMIT WITH SPECIFIC DETAILS AND | | | PRODUCT SUBMITTALS. | | | | | | PER NFPA 13D | | | | | | 5.3* UNDERGROUND PIPE. ANY TYPE OF PIPE OR TUBE | | | ACCEPTABLE | | | UNDER THE APPLICABLE PLUMBING CODE FOR UNDERGROUND | | | SUPPLY | | | PIPE SHALL BE ACCEPTABLE AS AN UNDERGROUND SUPPLY FOR A | | | FIRE | | | SPRINKLER SYSTEM WHEN INSTALLED BETWEEN THE POINT OF | | | CONNECTION | | | AND THE SYSTEM RISER. | | | | | | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND DETAILS | | | | | | | | | | | | 3) THERE IS NO INDICATIONS OF A DDCV. THE PER UTILITY | | | DEPT. THE FIRE SHALL SHALL HAVE IT'S OWN DDCV TO | | | PROTECT THE WATER SUPPLY. | | | | | | PLEASE REVIEW, CONTACT THEM AND ARRANGE FOR APPLICABLE | | | REQUIREMENTS. | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|