| Plan Review Notes For Permit 21071155 |
| Permit Number |
21071155 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-09-02 12:27:18 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A | | | BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH | | | CIRCUIT. NEC 250.32; | | | | | | FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A | | | DISCONNECTING MEANS AT THE BUILDING OR SEPARATE | | | STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR | | | MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31, | | | 225.32 | | | |
|