| 2022-05-23 13:34:40 | ELECTRIC REVIEW FAILED |
| | 1)PLEASE PROVIDE ELECTRICAL FLOOR PLAN REMOVED FROM |
| | VERSION 2. FBC 107.2 |
| | 2)IT APPEARS RISER DIAGRAM IS INCORRECT. IT DETAILS 2 |
| | SETS OF 3/0 CONDUCTORS TO A 125-AMP PANEL. IT DOES NOT |
| | DETAIL WHETHER, IF THEY REALLY EXIST, THEY ARE AL OR CU |
| | CONDUCTORS PLEASE DETAIL WHETHER THIS IS A MAIN PANEL |
| | OR A DISCONNECT ONLY. PLEASE DETAIL WHETHER A BRANCH |
| | CIRCUIT PANEL IS EXISTING ON THE INTERIOR OF THE MAIN |
| | HOUSE. NEC 215.5 AND FBC 107.2 |
| | 3) PLEASE DETAIL SMOKE/CARBON ALARMS AS REQUIRED FBC |
| | 553.883 |
| | 4) PLEASE DETAIL THE REQUIRED GROUNDING ELECTRODE |
| | SYSTEM AT PANEL B AS REQUIRED. NEC 250.32 |
| | 5) PLEASE DETAIL THE 2 REQUIRED SMALL APPLIANCE |
| | CIRCUITS REQUIRED AT THE KITCHEN AS REQUIRED NEC |
| | 210.11(C)(1) ON FLOOR PLAN AND LOAD CALCULATION |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |