| Plan Review Notes For Permit 21071146 |
| Permit Number |
21071146 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-08-31 14:29:40 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E-3.6.0 | | | | | | PANEL "H" UPGRADED TO 400 AMPS FROM 250 AMPS | | | ADDED LOADS OF TRASH COMPACTOR AND CAR CHARGERS | | | PANEL "MDP" ADDED SURGE PROTECTOR | | | PANEL LL UPGRADED TO 250 AMPS FROM 200 AMPS | | | ADDED LOADS OF ACCESS CONTROL, LANDSCAPE LIGHTING, CAR | | | CHAGERS, IRIGATION PUMPS | | | | | | NEED TO SUBMIT A NEW RISER DIAGRAM SHOWING NEW PANEL | | | AND WIRE SIZES | | | | | | NEED TO INCLUDE VALUE OF THE ADDITIONAL WORK | | | | | | NEED TO SUBMIT THE PERMIT NUMBERS FOR ALL THE | | | ADDITIONAL LOADS ADDED TO THESE PANELS |
|