| Plan Review Notes For Permit 21071145 |
| Permit Number |
21071145 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-10-12 13:09:32 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | MAIN ARE NOT GROUPED PER 230.72. THE INSTALLATION DOES | | | NOT MEET THE CODE. | | | | | | 230.72 GROUPING OF DISCONNECTS. | | | (A) GENERAL. THE TWO TO SIX DISCONNECTS AS PERMITTED IN | | | 230.71 SHALL BE GROUPED. EACH DISCONNECT SHALL BE | | | MARKED TO INDICATE THE LOAD SERVED. | | | | | | |
|