2021-10-12 13:09:32ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 MAIN ARE NOT GROUPED PER 230.72. THE INSTALLATION DOES
 NOT MEET THE CODE.
  
 230.72 GROUPING OF DISCONNECTS.
 (A) GENERAL. THE TWO TO SIX DISCONNECTS AS PERMITTED IN
 230.71 SHALL BE GROUPED. EACH DISCONNECT SHALL BE
 MARKED TO INDICATE THE LOAD SERVED.
  
  