2021-08-17 15:58:12ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-4.5.2 MASTER BEDROOM HAS PANEL IN CLOSET.
  
 240.24(D) NOT IN VICINITY OF EASILY IGNITIBLE MATERIAL.
 OVERCURRENT DEVICES SHALL NOT BE LOCATED IN THE
 VICINITY OF EASILY IGNITIBLE
 MATERIAL, SUCH AS IN CLOTHES CLOSETS.
  
 RISER HAS BEEN CHANGED IS THIS REVISED ON ANOTHER
 REVISION?
  
 CHARGERS SHOWN HAVE NOT BEEN PERMITTED AS OF TODAY.