2021-12-02 17:55:112ND REVIEW FBC-2020 PLUMBING
 PERMIT-21071140
 12/2/2021
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1. PROVIDE A CLEAR AND LEGIBLE PERMIT APPLICATION AND
 DRAWINGS FOR REVIEW.WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. SECOND REQUEST. THE CITY OF WEST PALM BEACH HAS NO
 RECORD OF EXISTING GAS PERMITS WITH INSPECTIONS OF THE
 CURRENT SYSTEM. A COMPLETE EVALUATION OF ALL GAS
 SYSTEMS AND EQUIPMENT WILL BE DONE AT THE FIELD, AND IF
 NOT TO CODE, IT MAY NEED TO BE BOUT UP TO CODE
 COMPLIANCE AT THE OWNER'S EXPENSE. PLEASE INCLUDE THE
 CURRENT AND NEW GAS SYSTEM AND EQUIPMENT IN THIS PERMIT
 FOR THIS SCOPE OF WORK PER THE WPB AMENDMENTS TO THE
 FBC SEC. 105.1.
  
 3. SECOND REQUEST. THERE ARE TWO TANKLESS WATER HEATERS
 ARE SHOWN, BUT THE PERMIT IS FOR A GENERATOR, AND IT IS
 NOT ON ISOMETRIC. WOULD YOU PLEASE CLARIFY WHICH IS
 CORRECT AND CHANGE THE DESCRIPTION ON THE PERMIT PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 4. SECOND REQUEST. A SEPARATE PERMIT IS REQUIRED FOR
 THE GENERATOR PER THE WPB AMENDMENTS TO THE FBC SEC.
 105.1.
  
 5. SECOND REQUEST. PLEASE SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES.
 SEC. G2421.1.
  
 6. SECOND REQUEST. THE CLAIMED VALUE APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION. WOULD YOU PLEASE
 PROVIDE A BONA FIDE SIGNED CONTRACT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 109.3 BUILDING PERMIT
 VALUATIONS?
  
 7. SECOND REQUEST. PLEASE SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS FOR THE GENERATOR OR TANKLESS. THE
 GENERATOR SHALL BE LISTED AND APPROVED PER THE NFPA 58
 SEC. 5.20.1. THE GENERATOR SHALL MEET THE REQUIREMENTS
 OF UL 2200.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  
  