| 2021-08-10 09:28:53 | 08/10/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF |
| | EXISTING GAS PERMITS WITH INSPECTIONS OF THE CURRENT |
| | SYSTEM. A COMPLETE EVALUATION OF ALL GAS SYSTEMS AND |
| | EQUIPMENT WILL BE DONE AT THE FIELD, AND IF NOT TO |
| | CODE, IT MAY NEED TO BE BOUT UP TO CODE COMPLIANCE AT |
| | THE OWNER'S EXPENSE. PLEASE INCLUDE THE CURRENT AND NEW |
| | GAS SYSTEM AND EQUIPMENT IN THIS PERMIT FOR THIS SCOPE |
| | OF WORK PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1. |
| | |
| | 2. THERE ARE TWO TANKLESS WATER HEATERS ARE SHOWN, BUT |
| | THE PERMIT IS FOR A GENERATOR, AND IT IS NOT ON |
| | ISOMETRIC. WOULD YOU PLEASE CLARIFY WHICH IS CORRECT |
| | AND CHANGE THE DESCRIPTION ON THE PERMIT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 3. A SEPARATE PERMIT IS REQUIRED FOR THE GENERATOR PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 105.1. |
| | |
| | 4. PLEASE SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR |
| | THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION PER THE 2020 FBC RES. SEC. G2421.1. |
| | |
| | 5. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON |
| | THE APPLICATION. WOULD YOU PLEASE PROVIDE A BONA FIDE |
| | SIGNED CONTRACT PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 109.3 BUILDING PERMIT VALUATIONS? |
| | |
| | 6. PLEASE SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR |
| | THE GENERATOR OR TANKLESS. THE GENERATOR SHALL BE |
| | LISTED AND APPROVED PER THE NFPA 58 SEC. 5.20.1. THE |
| | GENERATOR SHALL MEET THE REQUIREMENTS OF UL 2200. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |
| | |