| 2021-08-18 07:52:19 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 21071137 | | | 8/18/2021 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET 1.1: PLEASE SHOW THE WIDTH MEASUREMENTS OF THE | | | NEW COUNTERS- SECTION 308.3.1 FBC ACC. | | | | | | 2) 3.1: PLEASE ADD THE NEW SINKS AND FAUCETS TO THE | | | FIXTURE SCHEDULE- SECTIONS 418.1 & 424.1 FBC P. | | | | | | 3) 3.1: CORRECT THE 1/2-INCH HW PIPE INSULATION | | | THICKNESS TO MINIMUM 1-INCH PER TABLE C403.2.10 FBC EC. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|