Plan Review Notes
Plan Review Notes For Permit 21071098
Permit Number 21071098
Review Stop P
Sequence Number 2
Notes
Date Text
2021-10-26 14:10:401ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21071098
 10/26/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH NOTES ADDED IN CAP
 LETTERS.
  
 1) FAILED. SHEETS P1 & P2: REFER TO SECTION 1003.3.3.1
 FBC P AND REMOVE THE DRAINAGE FROM THE HAND SINKS, ICE
 MAKER, ICE BINS, AND WIC/WIF CONDENSATE FROM THE GREASE
 WASTE LINE. GREASE INTERCEPTORS SHALL RECEIVE DRAINAGE
 ONLY FROM FIXTURES AND EQUIPMENT WITH GREASE-LADEN
 WASTE. PLEASE RELOCATE HE DRAINAGE FROM THE ABOVE
 FIXTURES AND EQUIPMENT TO THE SANITARY LINE EXCEPT FOR
 THE CONDENSATE WHICH IS PROHIBITED FROM DRAINING INTO
 THE SYSTEM PER SEC. 90-126 WPB CODE OF ORDINANCES. THE
 CONDENSATE SHALL DRAIN INTO THE STORM SYSTEM, DRYWELL
 OR PERMEABLE GROUND. THE MOP SINK AND PREP SINK SHALL
 DRAIN INTO THE GREASE WASTE INTERCEPTOR- SECTION
 1003.3.1 FBC P.
  
 3) FAILED. P1 & P2: PROVIDE AN INDIRECT WASTE DETAIL
 FOR THE 3-COMPARTMENT SINK- SECTION 802.1.1 FBC P. EACH
 WELL OF THE 3-COMPARTMENT SINK SHALL DRAIN
 INDEPENDENTLY INTO THE FLOOR SINK- SECTION 802.1.1. FBC
 P.
  
 5) FAILED P1 & P2: PROVIDE A FILTERED WATER ISOMETRIC.
 SHOW THE TYPE OF PIPING, PIPING RUNS TO FIXTURES AND
 EQUIPMENT, AND LOCATIONS OF WATER HAMMER ARRESTORS AND
 BACKFLOW PREVENTERS- SECTIONS 604.9 & 608.3 FBC P.
 BACKFLOW PREVENTER IS REQUIRED FOR THE SUPPLY LINE TO
 THE FILTER (P17)- SECTION 608.3.1 FBC P.
  
 NEW COMMENTS.
  
 1) SHEET P1- WATER RISER: REMOVE THE ASSE 1024
 REFERENCE AT THE RPZA BY THE ICE MAKER. AN RPZ SHALL
 MEET THE ASSE 1013 STANDARD- TABLE 608.3 FBC P.
  
 2) P1 & P2: THE SUPPLY LINES TO THE DISPENSERS LISTED
 IN THE BACKFLOW MATRIX ON P2 ARE NOT SHOWN ON THE WATER
 RISER- SECTION 107.2.1 WPB.
  
 3) P2 BACKFLOW MATRIX: THE WATTS DCDA MODELS ARE NOT
 RPZ?S- PLEASE CORRECT- TABLE 608.3 FBC P. A) LIST THE
 MAKE AND MODEL OF THE DUAL CHECK VALVE LISTED AS 7 IN
 THE MATRIX- TABLE 608.3 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  