| 2021-10-26 14:10:40 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21071098 |
| | 10/26/21 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH NOTES ADDED IN CAP |
| | LETTERS. |
| | |
| | 1) FAILED. SHEETS P1 & P2: REFER TO SECTION 1003.3.3.1 |
| | FBC P AND REMOVE THE DRAINAGE FROM THE HAND SINKS, ICE |
| | MAKER, ICE BINS, AND WIC/WIF CONDENSATE FROM THE GREASE |
| | WASTE LINE. GREASE INTERCEPTORS SHALL RECEIVE DRAINAGE |
| | ONLY FROM FIXTURES AND EQUIPMENT WITH GREASE-LADEN |
| | WASTE. PLEASE RELOCATE HE DRAINAGE FROM THE ABOVE |
| | FIXTURES AND EQUIPMENT TO THE SANITARY LINE EXCEPT FOR |
| | THE CONDENSATE WHICH IS PROHIBITED FROM DRAINING INTO |
| | THE SYSTEM PER SEC. 90-126 WPB CODE OF ORDINANCES. THE |
| | CONDENSATE SHALL DRAIN INTO THE STORM SYSTEM, DRYWELL |
| | OR PERMEABLE GROUND. THE MOP SINK AND PREP SINK SHALL |
| | DRAIN INTO THE GREASE WASTE INTERCEPTOR- SECTION |
| | 1003.3.1 FBC P. |
| | |
| | 3) FAILED. P1 & P2: PROVIDE AN INDIRECT WASTE DETAIL |
| | FOR THE 3-COMPARTMENT SINK- SECTION 802.1.1 FBC P. EACH |
| | WELL OF THE 3-COMPARTMENT SINK SHALL DRAIN |
| | INDEPENDENTLY INTO THE FLOOR SINK- SECTION 802.1.1. FBC |
| | P. |
| | |
| | 5) FAILED P1 & P2: PROVIDE A FILTERED WATER ISOMETRIC. |
| | SHOW THE TYPE OF PIPING, PIPING RUNS TO FIXTURES AND |
| | EQUIPMENT, AND LOCATIONS OF WATER HAMMER ARRESTORS AND |
| | BACKFLOW PREVENTERS- SECTIONS 604.9 & 608.3 FBC P. |
| | BACKFLOW PREVENTER IS REQUIRED FOR THE SUPPLY LINE TO |
| | THE FILTER (P17)- SECTION 608.3.1 FBC P. |
| | |
| | NEW COMMENTS. |
| | |
| | 1) SHEET P1- WATER RISER: REMOVE THE ASSE 1024 |
| | REFERENCE AT THE RPZA BY THE ICE MAKER. AN RPZ SHALL |
| | MEET THE ASSE 1013 STANDARD- TABLE 608.3 FBC P. |
| | |
| | 2) P1 & P2: THE SUPPLY LINES TO THE DISPENSERS LISTED |
| | IN THE BACKFLOW MATRIX ON P2 ARE NOT SHOWN ON THE WATER |
| | RISER- SECTION 107.2.1 WPB. |
| | |
| | 3) P2 BACKFLOW MATRIX: THE WATTS DCDA MODELS ARE NOT |
| | RPZ?S- PLEASE CORRECT- TABLE 608.3 FBC P. A) LIST THE |
| | MAKE AND MODEL OF THE DUAL CHECK VALVE LISTED AS 7 IN |
| | THE MATRIX- TABLE 608.3 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |