| 2021-09-27 17:52:57 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21071098 |
| | 9/27/21 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P1 & P2: REFER TO SECTION 1003.3.3.1 FBC P |
| | AND REMOVE THE DRAINAGE FROM THE HAND SINKS, ICE MAKER, |
| | ICE BINS, AND WIC/WIF CONDENSATE FROM THE GREASE WASTE |
| | LINE. GREASE INTERCEPTORS SHALL RECEIVE DRAINAGE ONLY |
| | FROM FIXTURES AND EQUIPMENT WITH GREASE-LADEN WASTE. |
| | PLEASE RELOCATE HE DRAINAGE FROM THE ABOVE FIXTURES AND |
| | EQUIPMENT TO THE SANITARY LINE EXCEPT FOR THE |
| | CONDENSATE WHICH IS PROHIBITED FROM DRAINING INTO THE |
| | SYSTEM PER SEC. 90-126 WPB CODE OF ORDINANCES. THE |
| | CONDENSATE SHALL DRAIN INTO THE STORM SYSTEM, DRYWELL |
| | OR PERMEABLE GROUND. |
| | |
| | 2) P1 & P2: THE GREASE WASTE DRAINAGE LOAD FROM THE |
| | TENANT SPACE INTO THE EXISTING INTERCEPTOR APPEARS TO |
| | HAVE INCREASED. PROVIDE GREASE WASTE CALCULATIONS IN |
| | ACCORDANCE WITH SECTIONS 1003.3.4 OR 1003.3.6 FBC P. |
| | PLEASE INDICATE THE CAPACITY OF THE EXISTING |
| | INTERCEPTOR AND VERIFY NO INCREASE IN SIZE WILL BE |
| | REQUIRED. |
| | |
| | 3) P1 & P2: PROVIDE AN INDIRECT WASTE DETAIL FOR THE |
| | 3-COMPARTMENT SINK- SECTION 802.1.1 FBC P. |
| | |
| | 4) P1 & P2: SHOW THE LOCATIONS OF WATER HAMMER |
| | ARRESTORS IN THE RISER DRAWING- SECTION 604.9 FBC P. |
| | |
| | 5) P1 & P2: PROVIDE A FILTERED WATER ISOMETRIC. SHOW |
| | THE TYPE OF PIPING, PIPING RUNS TO FIXTURES AND |
| | EQUIPMENT, AND LOCATIONS OF WATER HAMMER ARRESTORS AND |
| | BACKFLOW PREVENTERS- SECTIONS 604.9 & 608.3 FBC P. |
| | |
| | 6) P1 & P2: SHOW THE SUPPLY LINE TO THE CHEMICAL |
| | DISPENSER IN THE DRAWINGS, AND THE TYPE OF BACKFLOW |
| | PREVENTER TO BE INSTALLED. SHOW THE MAKE AND MODEL IN |
| | THE SCHEDULE- SECTION 608.3 FBC P. |
| | |
| | 7) P1 & P2: PROVIDE THE EFFICIENCY RATING OF THE WATER |
| | HEATER- SECTION C404.2 FBC EC. PROVIDE AN ENLARGED |
| | WATER HEATER PIPING DETAIL SHOWING THE LOCATIONS OF |
| | CONTROL VALVES AND THE REQUIRED THERMAL EXPANSION TANK- |
| | SECTION 607.3 FBC P. |
| | |
| | 8) P2: REFER TO TABLE C403.2.10 FBC EC AND CORRECT NOTE |
| | 4 INDICATING THE 1/2-INCH THICK PIPE INSULATION. |
| | |
| | 9) P1 & P2: PLACE A NOTE TO INDICATE A SEPARATE PERMIT |
| | IS REQUIRED FOR THE WATER SERVICE BACKFLOW PREVENTER- |
| | SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |