2021-09-27 17:52:571ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21071098
 9/27/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P1 & P2: REFER TO SECTION 1003.3.3.1 FBC P
 AND REMOVE THE DRAINAGE FROM THE HAND SINKS, ICE MAKER,
 ICE BINS, AND WIC/WIF CONDENSATE FROM THE GREASE WASTE
 LINE. GREASE INTERCEPTORS SHALL RECEIVE DRAINAGE ONLY
 FROM FIXTURES AND EQUIPMENT WITH GREASE-LADEN WASTE.
 PLEASE RELOCATE HE DRAINAGE FROM THE ABOVE FIXTURES AND
 EQUIPMENT TO THE SANITARY LINE EXCEPT FOR THE
 CONDENSATE WHICH IS PROHIBITED FROM DRAINING INTO THE
 SYSTEM PER SEC. 90-126 WPB CODE OF ORDINANCES. THE
 CONDENSATE SHALL DRAIN INTO THE STORM SYSTEM, DRYWELL
 OR PERMEABLE GROUND.
  
 2) P1 & P2: THE GREASE WASTE DRAINAGE LOAD FROM THE
 TENANT SPACE INTO THE EXISTING INTERCEPTOR APPEARS TO
 HAVE INCREASED. PROVIDE GREASE WASTE CALCULATIONS IN
 ACCORDANCE WITH SECTIONS 1003.3.4 OR 1003.3.6 FBC P.
 PLEASE INDICATE THE CAPACITY OF THE EXISTING
 INTERCEPTOR AND VERIFY NO INCREASE IN SIZE WILL BE
 REQUIRED.
  
 3) P1 & P2: PROVIDE AN INDIRECT WASTE DETAIL FOR THE
 3-COMPARTMENT SINK- SECTION 802.1.1 FBC P.
  
 4) P1 & P2: SHOW THE LOCATIONS OF WATER HAMMER
 ARRESTORS IN THE RISER DRAWING- SECTION 604.9 FBC P.
  
 5) P1 & P2: PROVIDE A FILTERED WATER ISOMETRIC. SHOW
 THE TYPE OF PIPING, PIPING RUNS TO FIXTURES AND
 EQUIPMENT, AND LOCATIONS OF WATER HAMMER ARRESTORS AND
 BACKFLOW PREVENTERS- SECTIONS 604.9 & 608.3 FBC P.
  
 6) P1 & P2: SHOW THE SUPPLY LINE TO THE CHEMICAL
 DISPENSER IN THE DRAWINGS, AND THE TYPE OF BACKFLOW
 PREVENTER TO BE INSTALLED. SHOW THE MAKE AND MODEL IN
 THE SCHEDULE- SECTION 608.3 FBC P.
  
 7) P1 & P2: PROVIDE THE EFFICIENCY RATING OF THE WATER
 HEATER- SECTION C404.2 FBC EC. PROVIDE AN ENLARGED
 WATER HEATER PIPING DETAIL SHOWING THE LOCATIONS OF
 CONTROL VALVES AND THE REQUIRED THERMAL EXPANSION TANK-
 SECTION 607.3 FBC P.
  
 8) P2: REFER TO TABLE C403.2.10 FBC EC AND CORRECT NOTE
 4 INDICATING THE 1/2-INCH THICK PIPE INSULATION.
  
 9) P1 & P2: PLACE A NOTE TO INDICATE A SEPARATE PERMIT
 IS REQUIRED FOR THE WATER SERVICE BACKFLOW PREVENTER-
 SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  