| Plan Review Notes For Permit 21071092 |
| Permit Number |
21071092 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-08-28 08:13:59 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21071092 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE SUBMIT THE OUTDOOR AIR CALCULATIONS FOR EACH | | | USE OF SPACE, EACH SPACE WILL REQUIRE A CERTAIN AMOUNT | | | OF OUTDOOR AIR PLEASE SHOW THAT CFM NUMBER FOR EACH | | | SPACE. I.E. LARGE CONFERENCE ROOM (18A19) 168 SQ | | | FT/1000 = .168; .168 X 50 = 8.4; 8.4 X 5 = 42; 168 X | | | .06 = 10.08; 42 + 10.08 = 52.08 CFM OF OUTDOOR AIR | | | REQUIRED. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|