2021-08-28 08:13:591ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21071092
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SUBMIT THE OUTDOOR AIR CALCULATIONS FOR EACH
 USE OF SPACE, EACH SPACE WILL REQUIRE A CERTAIN AMOUNT
 OF OUTDOOR AIR PLEASE SHOW THAT CFM NUMBER FOR EACH
 SPACE. I.E. LARGE CONFERENCE ROOM (18A19) 168 SQ
 FT/1000 = .168; .168 X 50 = 8.4; 8.4 X 5 = 42; 168 X
 .06 = 10.08; 42 + 10.08 = 52.08 CFM OF OUTDOOR AIR
 REQUIRED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  