Plan Review Notes
Plan Review Notes For Permit 21071092
Permit Number 21071092
Review Stop P
Sequence Number 1
Notes
Date Text
2021-08-17 14:57:551ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21071092
 8/17/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A3.01 & A3.02- MISSING OR INCORRECT
 ACCESSIBLE PLUMBING FIXTURE DETAILS FOR THE BATHROOMS
 PER FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- 606.2.
 C) TURNING SPACE DIAGRAMS AND DIMENSIONS- 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- 604.2.
 E) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER
 SURFACES FROM THE FINISHED FLOOR- 606.3.
 F) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- 603.3
 G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- 604.5 & 609.4, FIGURES 604.
 PLEASE SHOW THE MINIMUM AND MAXIMUM DIMENSIONS AS SHOWN
 IN THE FIGURES.
 H) REMOVE THE VERTICAL GRAB BAR SHOWN IN THE DETAIL.
 GRAB BARS SHALL BE INSTALLED IN HORIZONTAL POSITIONS-
 609.4
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7. THE DRAWING DOES NOT SHOW THE MEASUREMENT
 TO THE CENTER OF THE DISPENSER.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2
  
 2) SHEETS A3.01 & A3.02- MISSING OR INCORRECT
 ACCESSIBLE SHOWER DETAILS PER FBC ACC:
 A) CLEAR INSIDE DIMENSIONS- SECTION 608.2.1
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS- 608.2.1.
 C) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- 608.3 AND 608.3.1
 D) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE
 SHOWER- 608.5.1 & FIGURE 608.5.1. THE DRAWING SHOWS THE
 LOCATION OF THE CONTROL, FAUCET, AND SPRAY IN THE WRONG
 LOCATION.
 E) SHOWER SPRAY UNIT SPECIFICATIONS- 608.6.
 F) LOCATION OF ACCESSIBLE SHOWER SEAT AND MOUNTING
 DETAILS- 610.3 & 610.3.2. & FIGURE 610.3.2.
 G) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE SINK
 AND SINK MOUNTING HEIGHT- 606.2 & 606.3.
  
 3) A3.03: SHOW THE CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSION FOR THE SINK- 606.2.
  
 4) A3.03 & A3.04: A) CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSION FOR THE SINK AND SINK MOUNTING HEIGHT- 606.2
 & 606.3. B) REACH RANGES AND OPERABLE PARTS FOR THE
 COFFEE MAKER AND DISPENSER- 308. SUBMIT MANUFACTURER'S
 SPECIFICATIONS TO VERIFY COMPLIANCE.
  
 5) A1.116: SHOW THE INTERIOR DIMENSIONS OF THE NEW
 WATER CLOSET COMPARTMENT IN THE MEN'S BATHROOM- SECTION
 405.3.1 FBC P.
  
 6) REFER TO SECTION 310.3 FBC P AND SECTION 1210.2.2
 AND INDICATE THE TYPE OF WALL FINISH SURROUND MATERIAL
 TO BE INSTALLED AT THE MOP SINK
 WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIALS USED IN SUCH WALLS SHALL BE OF
 A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  