| Plan Review Notes For Permit 21071092 |
| Permit Number |
21071092 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-08-17 11:25:32 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) IN THE CAFE ANY OUTLET WITHIN 6' OF THE SINK TO BE | | | GFCI PROTECTED 210.8(B) | | | | | | 2) ANY CONFERENC ROOM LESS THAN 100 SQ. FT. SHALL HAVE | | | WALL OUTLETS INSTALLED PER 210.71(B)(1) | | | | | | 3) ANY CONFERENCE ROOM MORE THAN 214 SQ. FT. SHALL HAVE | | | FLOOR OUTLET(S) INSTALLED PER 210.71(B)(2) | | | | | | 4) ANY OUTLET WITHIN 6' OF ANY SINK SHALL BE GFCI | | | PROTECTED PER 210.8(B)(5) | | | | | | 5) PANEL NL16A NOT SHOWN ON RISER DIAGRAM 215.5 | | | | | | 6) PANEL NL 16A DOES NOT HAVE A PANEL SHCEDULE FOR | | | REVIEW. |
|