| 2021-08-17 11:56:58 | OFFICE BUILDOUT |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | 1) PLEASE PROVIDE A FINISH SCHEDULE. |
| | 2) FBC 1210.2.2 WALLS AND PARTITIONS. |
| | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR |
| | STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS |
| | SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY |
| | MOISTURE. (DRYWALL IS NOT CONSIDERED A HARD SURFACE) |
| | 3) FBC 1210.2.1 FLOORS AND WALL BASES. |
| | IN OTHER THAN DWELLING UNITS, TOILET, BATHING AND |
| | SHOWER ROOM FLOOR FINISH MATERIALS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE. THE INTERSECTIONS OF SUCH |
| | FLOORS WITH WALLS SHALL HAVE A SMOOTH, HARD, |
| | NONABSORBENT VERTICAL BASE THAT EXTENDS UPWARD ONTO THE |
| | WALLS NOT LESS THAN 4 INCHES (102 MM). |
| | 4) FBC 1210.2.3 SHOWERS. |
| | SHOWER COMPARTMENTS AND WALLS ABOVE BATHTUBS WITH |
| | INSTALLED SHOWER HEADS SHALL BE FINISHED WITH A SMOOTH, |
| | NONABSORBENT SURFACE TO A HEIGHT NOT LESS THAN 72 |
| | INCHES (1829 MM) ABOVE THE DRAIN INLET. |
| | 5) PLEASE SHOW THE ACCESSIBLE SEATING IN THE CAFE FBC |
| | A226.1 GENERAL. |
| | WHERE DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION |
| | OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING |
| | SPACES AND STANDING SPACES AT THE DINING SURFACES SHALL |
| | COMPLY WITH 902. |
| | 6) PLEASE SHOW THE GRAB BAR SIZES AND LOCATION |
| | DIMENSIONS AT THE SHOWER TO COMPLY WITH FBC 608.3.2 |
| | 7) PLEASE SHOW THE SHOWER SEAT SIZE AND LOCATION |
| | DIMENSIONS TO COMPLY WITH FBC A610.3 |
| | 8) RAMPS ARE SHOWN IN DIFFERENT AREAS ON DRAWING A1.116 |
| | - PLEASE SHOW THE LANDINGS AT DOORS TO COMPLY WITH FBC |
| | A404.2.4.4 FLOOR OR GROUND SURFACE. |
| | FLOOR OR GROUND SURFACE WITHIN REQUIRED MANEUVERING |
| | CLEARANCES SHALL COMPLY WITH 302. CHANGES IN LEVEL ARE |
| | NOT PERMITTED. |
| | 9) PLEASE SHOW RAMP LENGTHS AND RISE TO DETERMINE IF A |
| | HANDRAIL IS REQUIRED PER FBC A405.8 HANDRAILS. |
| | RAMP RUNS WITH A RISE GREATER THAN 6 INCHES (150 MM) |
| | SHALL HAVE HANDRAILS COMPLYING WITH 505. |
| | 10) THE TOILET PAPER HOLDER LOCATION DIMENSIONS FROM |
| | THE FRONT OF THE TOILET SEAT IS SHOWN INCORRECTLY FOR |
| | AN ACCESSIBLE RESTROOM FBC A604.7 |
| | 11) THE MIRROR DIMENSIONS FROM THE FLOOR SHOULD BE TO |
| | THE "REFLECTIVE SURFACE" FOR AN ACCESSIBLE RESTROOM PER |
| | FBC A603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |