| Plan Review Notes For Permit 21071042 |
| Permit Number |
21071042 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-07-24 10:18:35 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC B 1010.1.10, PROVIDE THE OCCUPANCY | | | CLASSIFICATIONS THAT THIS BUILDING SERVES. IF THIS | | | BUILDING INCLUDES ASSEMBLY OCCUPANCY (SUCH AS AN | | | AUDITORIUM OR A CAFETERIA) AND THE OCCUPANT LOAD IS 50 | | | OR MORE, PANIC HARDWARE IS REQUIRED. REVISE THE PLAN TO | | | SHOW OCCUPANCY CLASSIFICATIONS AND OCCUPANT LOAD FOR | | | THOSE OCCUPANCIES, OR REVISE DOCUMENTS TO INCLUDE PANIC | | | HARDWARE. | | | | | | 2. FBC A 404.2.5, PAGE 9 OF THE DOOR PRODUCT APPROVAL | | | PROPSES A 4" BUMPER THRESHOLD WITH A STATEMENT THAT | | | "ADA COMPLIANT TO BE REVIEWED BY BUILDING OFFICIAL". | | | THIS PERMIT WILL BE REDLINED THAT COMPLIANCE WILL BE | | | FIELD VERIFIED. | | | | | | THRESHOLD SHALL BE 1/2" MAX. | | | | | | |
|