| 2021-08-23 18:04:33 | 08/23/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON A001, UNDER GENERAL NOTES, # 1 HAS 2017, AND IT |
| | SHOULD BE 2020 PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. ON SHEET A003; |
| | |
| | A. THE REFLECTIVE PART OF THE MIRROR NEEDS TO BE 4 |
| | INCHES TO THE REFLECTIVE SIDE PER THE 2020 FBC ACC SEC. |
| | 603.3. |
| | |
| | B. THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE |
| | GRIPPING SURFACE PER THE 2020 FBC ACC SEC. 609.4. |
| | |
| | C. THE TOILET PAPER DISPENSERS SHALL BE 7 INCHES |
| | MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE WATER |
| | CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER PER |
| | THE 2020 FBC ACC SEC. 604.7. |
| | |
| | D. WOULD YOU, PLEASE SHOW THE 30 INCHES BY 48 INCHES |
| | INSIDE THE RUNNING RADIUS PER THE 2020 FBC ACC SEC. 305 |
| | CLEAR FLOOR OR GROUND SPACE. |
| | |
| | 3. ON SHEET A150, UNDER GENERAL DEMOLITION NOTES, # 2 |
| | HAS 2017, AND IT SHOULD BE 2020 PER THE WPB AMENDMENTS |
| | TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 4. ON SHEETS A201 A251 AND A 801; THE STALL IN THE |
| | WOMEN AND MEN'S RESTROOM DOES NOT SHOW A WATER CLOSET; |
| | |
| | A. PLEASE PROVIDE THE CLEAR FLOOR SPACE FOR THE TOILET |
| | THAT WILL BE IN THE TOILET STALL, URINAL, AND LAVS |
| | OUTSIDE STALL PER THE FLORIDA BUILDING CODE AND FLORIDA |
| | ACCESSIBILITY CODE. |
| | |
| | B. PLEASE SHOW ALL CLEAR FLOOR SPACE DIMENSIONS PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS AND 2020 FBC ACC SEC. 606.2. 2 |
| | CLEAR FLOOR SPACE. |
| | |
| | 5. ON SHEET A250, UNDER PLUMBING FIXTURES TABLE 2017, |
| | IT SHOULD BE 2020 PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | THERE ARE TWO OR MORE LOCATIONS WITH 2017 ON AS WELL. |
| | |
| | 6. ON SHEET A801; |
| | A. ON FIXTURE ELEVATION, THE TOILET SHALL BE 1 FOOT 6 |
| | INCHES TO 1 FOOT 8 INCHES AND ONLY 1 FOOT 6 INCHES |
| | SHOW. WOULD YOU PLEASE ADD THE VARIANCE PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | B. THE WATER CLOSET IN THE BACK WALL GRAB BAR SHALL BE |
| | 1 INCHES FROM THE CENTER OF THE WATER CLOSET TO THE |
| | SIDE OF THE GRAB BAR AND 2 FEET TO THE OTHER SIDE PER |
| | THE 2020 ACC 604.5.2 REAR WALL. |
| | |
| | C. WOULD YOU PLEASE SHOW THE BOTTOM ON THE LAV, WHICH |
| | SHALL BE A MINIMUM OF 27 INCHES KNEE CLEARANCE PER THE |
| | 2020 FBC SEC. 306.3. |
| | |
| | D. THE WATER CLOSET CONTROL FLUSH SHALL BE ON THE OPEN |
| | SIDE CONTROL PER THE 2020 FBC SEC. 604.6 FLUSH |
| | CONTROLS. |
| | |
| | E. HANDICAP CAP WATER CLOSET FLUSH CONTROL SHALL BE |
| | HAND OPERATED OR AUTOMATIC AND SHALL BE 36 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR AND ON THE OPEN SIDE PER |
| | THE 2020 FBC ACC SEC. 604.9.5. |
| | |
| | F. WOULD YOU, PLEASE SHOW THE CLEAR FLOOR SPACE SHALL |
| | BE 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE |
| | SIDEWALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR |
| | FROM THE REAR WALL PER THE 2020 FBC ACC. SEC. 604.3.1. |
| | |
| | G. LAVATORY WATER SUPPLY AND DRAINPIPES UNDER THE SIDE |
| | SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT |
| | AGAINST CONTACT PER THE 2020 FBC ACC SEC. 606.5. |
| | |
| | H. PLEASE SHOW OR MENTION THAT THE DOOR HANDLE HARDWARE |
| | SHOULD BE ON BOTH SIDES OF THE DOOR PER THE 2020 FBC |
| | ACC SEC. 404.2.7. |
| | |
| | I. WOULD YOU PLEASE SHOW THE HEIGHT OF THE PARTITION OF |
| | THE URINAL PER THE 2020 FBC SEC. P 405.3.5. |
| | |
| | J. WOULD YOU PLEASE SHOW THE HEIGHT OF THE LAV IN THE |
| | OPEN AREA AT 34 INCHES MAXIMUM PER THE 2020 FBC ACC |
| | SEC. 606.3. |
| | |
| | K. WOULD YOU, PLEASE SHOW THE MIRROR'S REFLECTIVE PART, |
| | WHICH NEEDS TO BE 4 INCHES TO THE REFLECTIVE SIDE PER |
| | THE 2020 FBC ACC SEC. 603.3. |
| | |
| | L. WATER CLOSET COMPARTMENT SHALL BE LOCATED IN THE |
| | CORNER, DIAGONAL TO THE DOOR 604.8.1.7 WATER CLOSET. |
| | |
| | 7. ON SHEET P.01; |
| | A.. UNDER PLUMBING NOTES 31, IT HAS THE 6 TH EDITION |
| | MENTION. THE 7 TH EDITION IS THE CORRECT ONE. WOULD YOU |
| | PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL |
| | SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE |
| | 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P |
| | 310.3. WOULD YOU PLEASE MAKE A NOTE ON THIS SHEET? |
| | |
| | C. ICEMAKER AND COFFEE MAKER SHALL BE EQUIPPED WITH AN |
| | IN-LINE VACUUM BREAKER THAT COMPLIES WITH ASSE 1024 PER |
| | THE 2020 FBC SEC. 608.13.10. |
| | |
| | D. SODA MACHINES SHALL BE EQUIPPED WITH AN IN-LINE |
| | VACUUM BREAKER THAT COMPLIES WITH ASSE 1022 PER THE |
| | 2020 FBC SEC. 608.17.1.1. |
| | |
| | E. WOULD YOU PLEASE DELETE OR STRIKE THROUGH THE |
| | ECLECTIC WATER COOLER WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 8. ON SHEET P0.2; |
| | A. WOULD YOU PLEASE PROVIDE DETAIL FOR THE FOOD |
| | HANDLING THREE-COMPARTMENT W/AIR GAP PER THE 2020 FBC |
| | SEC. P 802.1.1. |
| | |
| | B. THE GAS DETAIL SHOWS A CONDENSATE NEUTRALIZER THAT |
| | IS NOT PERMITTED PER THE AJH IN THE CITY OF WEST PALM |
| | BEACH AS IT IS NEVER KEPT OR MAINTAINED. WOULD YOU |
| | PLEASE SHOW WHERE THE CONDENSATE WILL DRAIN AND PLEASE |
| | SEPARATE CONDENSATE TO DUMP TO A LOCATION IN A SAFE |
| | PLACE PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | C. WOULD YOU PLEASE SHOW ON THIS PAGE THE ISOMETRIC THE |
| | SHUT OFF VALVES ON EACH SIDE OF THE RECALCULATING PUMP |
| | PER THE 2020 FBC SEC. 606.2 LOCATION OF SHUTOFF VALVES. |
| | |
| | 9. ON SHEET P2-1 AND P3-1; |
| | A. IN THE BAR AREA SHOWS BAR SINKS AND ICE MACHINES |
| | INTO THE GREASE INTERCEPTOR THAT IS NOT WASTER AND DO |
| | NOT REQUIRE TREATMENT AND ARE NOT APPROVED PER THE 2020 |
| | FBC SEC. P1003.2. |
| | |
| | B. IN THE RESTAURANT OTHER THAN THE BAR AREA, THERE ARE |
| | SEVERAL HAND SINKS K 15, B16, B46, K87, AND ICE |
| | BIN/CUBER K38, B10, AND B4 INTO THE GREASE INTERCEPTOR |
| | THAT ARE NOT WASTER AND DO NOT REQUIRE TREATMENT, AND |
| | ARE NOT APPROVED PER THE 2020 FBC SEC. P1003.2. |
| | |
| | C. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL |
| | SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE |
| | 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P |
| | 310.3. WOULD YOU PLEASE MAKE A NOTE ON THIS SHEET? |
| | |
| | D. SODA DRINKING BEVERAGE MACHINES SHALL BE PROTECTED |
| | WITH A DEVICE THAT COMPLIES WITH ASSE 1022 SHALL HAVE |
| | CARBONATED DISCHARGED TO A SAFE LOCATION PER THE 2020 |
| | FBC SEC. P 608.17.1.1. |
| | |
| | E. THE COFFEE MAKER/ICE MAKER REQUIRES AN INLINE VACUUM |
| | BREAKER THAT COMPLIES WITH THE ASSE 1024 NON-CARBONATED |
| | PER THE 2020 FBC SEC. 608.17.1.2. |
| | |
| | 10. ON SHEET P6.1; |
| | A. HOT WATER LINES NOT IN CONDITION SPACE IN THE GROUND |
| | NEED TO BE INSULATED WITH A MINIMUM R-3 PER THE 2020 |
| | FBC SEC. RE 403.5.3. |
| | |
| | B. THE LINES TO EACH FIXTURE FROM THE RECIRCULATING |
| | MANIFOLD TO THE HOT WATER LINES SHALL BE SUPPLIED TO |
| | THE SOURCE; PLEASE REFER TO THE 2020 FBC ENERGY CODE |
| | TABLE C404.5.1. MAXIMUM ALLOWABLE PIPE LENGTH METHOD. |
| | |
| | C. IN THE KEYNOTES, TEMPERED WATER SHALL BE DELIVERED |
| | THROUGH AN APPROVED WATER-TEMPERATURE LIMITING DEVICE |
| | THAT CONFORMS TO ASSE 1070 OR CSA B125.3 PER THE 2020 |
| | FBC SEC. 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING |
| | FACILITIES. |
| | |
| | D. THE PIPING SHALL BE INSULATED TO LEVELS SHOWN IN |
| | TABLE C403.2.10 PER THE 2020 FBC EC 404.4 INSULATION OF |
| | PIPING. |
| | |
| | E. IN THE KITCHEN AREA, THERE IS A THREE-COMPARTMENT |
| | SINK. PLEASE PROVIDE DETAIL ON THE DRAINS TO AN |
| | INDIRECT WASTE INDEPENDENTLY FROM EACH OTHER PER THE |
| | 2017 FBC SEC. P 802.1.1. |
| | |
| | F. THERE IS TWO GAS UNIT FOR GAS UP ON THE MEZZANINE |
| | THAT MAY REQUIRE VENTING AND CONDENSATION. WOULD YOU |
| | PROVIDE MANUFACTURE SPECIFICATION ON HOW THESE ITEM IS |
| | BEING EXTORTED OUT THE STRUCTURE PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 11. ON SHEET A001 IN THE SHEET INDEX, IT CALLS OUT FOR |
| | SHEET P3.2 MEZZANINE PLUMBING PLAN, AND NONE WAS FOUND. |
| | WOULD YOU PLEASE PROVIDE PER THE WPB AMENDMENTS TO THE |
| | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 12. IT MENTIONS A GREASE INTERCEPTOR. WOULD YOU PLEASE |
| | PROVIDE THE CAPACITY OF THE EXISTING INTERCEPTOR IN |
| | GALLONS? |
| | A. IS IT SHARED WITH OTHER RESTAURANTS, AND IF SO, WHAT |
| | IS THEIR VOLUME. |
| | B. IS IT A PASSIVE HYDRO-MECHANICAL - OR GRAVITY-TYPE |
| | GREASE INTERCEPTOR MADE OF CONCRETE STEEL OR |
| | FIBERGLASS? |
| | C. IF APPLICABLE, WOULD YOU PLEASE PROVIDE THE STANDARD |
| | BEING USED FOR SIZING OF THE GREASE INTERCEPTOR? THE |
| | INTERCEPTOR SHALL BE SIZED IN ACCORDANCE WITH ONE OF |
| | THE STANDARDS LISTED IN 2020 FBC SEC. P 1003.3.5 OR |
| | RULE 64E-6 OF THE FLORIDA ADMINISTRATIVE CODE AND THE |
| | CITY OF WEST PALM BEACH STANDARD DETAIL GS-7. |
| | |
| | 13. SUBMIT LISTED FIRE-STOPPING DETAILS FOR THE PIPPING |
| | THROUGH RATED WALLS OR THE FLOORS. PLEASE SUBMIT THE |
| | COMPLETE ASSEMBLY DETAILS FOR THE SYSTEMS PER THE WPB |
| | AMENDMENTS TO FBC SEC. 107.2.1. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME ON ANY OF THE COMMENTS |
| | BY PHONE OR ZOOM MEETING IF YOU LIKE. |
| | |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |