| 2021-08-16 07:50:23 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21071035 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE ADD A NOTE TO THE DRAWINGS STATING THAT THE |
| | HOODS WILL REQUIRE A SEPARATE APPLICATION, REVIEW AND |
| | DRAWINGS. THE HOODS WILL NOT BE REVIEWED UNDER THIS |
| | PERMIT. |
| | |
| | 2) PLEASE ADD A NOTE TO THE DRAWINGS STATING THAT THE |
| | REFRIGERATION WILL REQUIRE A SEPARATE APPLICATION, |
| | REVIEW AND DRAWINGS. THE REFRIGERATION WILL NOT BE |
| | REVIEWED UNDER THIS PERMIT. |
| | |
| | 3) SHEET M2.2: IT APPEARS THAT THE ROOM LABELED CLOSET |
| | IS BEING USED FOR A RETURN AIR PATH. RETURN AIR SHALL |
| | NOT BE TAKEN FROM A CLOSET. FBC M 601.5 (7) |
| | |
| | 4) PLEASE PROVIDE A MECHANICAL FLOOR PLAN FOR THE |
| | RESTAURANT. FBC 107.2.1 |
| | |
| | 5) THE MINIMUM REQUIRED OUTDOOR AIR FOR THE DINING ROOM |
| | IS 2504 CFM; THE KITCHEN MINIMUM OUTDOOR AIR IS 434 |
| | CFM. FBC 403.3.1.1 AND TABLE 403.3.1.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |