| 2021-08-24 09:28:48 | 08/24/21 2ND LP GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET P6.1; |
| | A. WOULD YOU PLEASE SHOW THE LENGTH OF ALL CUT SECTIONS |
| | OF PIPE PER 2020 FBC FG SECS. 402.4.1, 402.4.2. |
| | |
| | B. THE REFERENCE CODE IS SHOWING 2017, AND THE CURRENT |
| | IS 2020. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | C. WOULD YOU PLEASE SHOW THE TYPE OF GAS (LP OR |
| | NATURAL) PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | D. MOST TANK-LESS UNITS CALL FOR A 10.5 INCHES WATER |
| | COLUMN, AND THE SERVICE METER DISCHARGES IS A 12 INCH |
| | WATER COLUMN REQUIRING A REGULATOR FOR THIS UNIT AS PER |
| | THE MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. |
| | SEC. 410.1. |
| | |
| | E. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE, |
| | TERMINATION POINT, HEIGHT ABOVE THE ROOF, AND ANCHORING |
| | DETAILS OF THE GAS VENT(S) FOR TANK-LESS PER THE 2020 |
| | FBC FG SECS. 502 THRU 505. |
| | |
| | F. WOULD YOU PLEASE SUBMIT THE MANUFACTURER'S |
| | SPECIFICATION SHEETS/INSTALLATION MANUAL FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC FG SEC. |
| | 305.1. |
| | |
| | G. WOULD YOU PLEASE SHOW ALL UNIONS IN FRONT OF |
| | REGULATOR 1' (FOOT) OF EITHER SIDE PER THE 2020 FBC FG |
| | SEC 410.2. |
| | |
| | H. WOULD YOU PLEASE LABEL AND SHOW DRIP LEG IS REQUIRED |
| | BEFORE THE EQUIPMENT IS INSTALLED AT TWO POINTS PER THE |
| | 2020 FBC FG 408.2 OR 2020 FBC RES. SEC. G2419.2. |
| | |
| | I. THE EMERGENCY HOOD SHUT DOWN SHUTOFF VALVE SHALL BE |
| | BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE |
| | UPSTREAM. UNION TO BE DOWNSTREAM OF MANUAL VALVE. SECS. |
| | 10.4, 10.5 OF NFPA 96-08. |
| | |
| | K. THERE IS A SECTION OF PIPE THAT DOES NOT HAVE SIZE. |
| | IS IT 1 1/4 INCHES OR 1 1/2 INCHES? WOULD YOU PLEASE |
| | CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |