| Plan Review Notes For Permit 21071007 |
| Permit Number |
21071007 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-07-21 14:15:47 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | FBC R 301: | | | | | | 1. ON THE INSTALLATION SCHEDULE IT STATES THAT THE | | | SUBSTRATE IS CONCRETE/BLOCK. DOES THAT MEAN CONCRETE ON | | | THE TOP, BLOCK ON THE BOTTOM, OR CONCRETE BLOCK? | | | | | | PAGE 6, THE TRAPPED MOUNT IS CIRCLED. AT THE TOP POURED | | | CONCRETE IS REQUIRED, SPACING CAN BE 24" PER THE | | | DETAIL. THEREFORE IT APPEARS THAT THE ANCHOR SPACING | | | PROPOSED IS FOR THE SIDES. | | | | | | PAGE 8 BUILDOUT MOUNT IS CIRCLED, IT REFERS TO ANCHOR | | | CHARTS ON SHEETS 17 AND 15, THIS ALLOWS FOR FILLED | | | CONCRETE BLOCK SUBSTRATE, NOTHING ON PAGES 17 AND 18 | | | ARE CIRCLED. | | | | | | PAGE 16 ANCHOR SPACING FOR TRAPPED MOUNT IS CIRCLED. | | | SUBSTRATE IS REQUIRED TO BE POURED CONCRETE (NOT BLOCK, | | | NOT FILLED CELL BLOCK). | | | | | | PLEASE CORRELATE THE ANCHOR SCHEDULE, THE MARKUPS ON | | | THE PRODUCT APPROVAL, AND THE PROPOSED INSTALLATION. | | | |
|