2021-07-21 14:15:47****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC R 301:
  
 1. ON THE INSTALLATION SCHEDULE IT STATES THAT THE
 SUBSTRATE IS CONCRETE/BLOCK. DOES THAT MEAN CONCRETE ON
 THE TOP, BLOCK ON THE BOTTOM, OR CONCRETE BLOCK?
  
 PAGE 6, THE TRAPPED MOUNT IS CIRCLED. AT THE TOP POURED
 CONCRETE IS REQUIRED, SPACING CAN BE 24" PER THE
 DETAIL. THEREFORE IT APPEARS THAT THE ANCHOR SPACING
 PROPOSED IS FOR THE SIDES.
  
 PAGE 8 BUILDOUT MOUNT IS CIRCLED, IT REFERS TO ANCHOR
 CHARTS ON SHEETS 17 AND 15, THIS ALLOWS FOR FILLED
 CONCRETE BLOCK SUBSTRATE, NOTHING ON PAGES 17 AND 18
 ARE CIRCLED.
  
 PAGE 16 ANCHOR SPACING FOR TRAPPED MOUNT IS CIRCLED.
 SUBSTRATE IS REQUIRED TO BE POURED CONCRETE (NOT BLOCK,
 NOT FILLED CELL BLOCK).
  
 PLEASE CORRELATE THE ANCHOR SCHEDULE, THE MARKUPS ON
 THE PRODUCT APPROVAL, AND THE PROPOSED INSTALLATION.
  