Notes
Date Text
2021-08-05 08:04:01ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) ROOFING SYSTEM CIRCLED TO BE USED ON THE PROVIDED
 PRODUCT APPROVAL DOES NOT MEET THE REQUIRED WIND
 PRESSURES PER FBC R TABLE R301.2(2) - - - WHEN CHOOSING
 A DIFFERENT ROOF SYSTEM PLEASE KEEP IN MIND TO REVIEW
 THE NOTES ON THE PRODUCT APPROVAL - NOTE NUMBER 9 ON
 THE PRODUCT APPROVAL - ADDITIONAL SIGNED AND SEALED
 ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR
 ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER PRESSURE
 THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL.
  
 FYI - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO
 BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR -
 IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN
 ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DIVISION AT THE CITY HALL.
  
  