| Plan Review Notes For Permit 21070982 |
| Permit Number |
21070982 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-08-05 08:04:01 | ROOFING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - | | | 1) ROOFING SYSTEM CIRCLED TO BE USED ON THE PROVIDED | | | PRODUCT APPROVAL DOES NOT MEET THE REQUIRED WIND | | | PRESSURES PER FBC R TABLE R301.2(2) - - - WHEN CHOOSING | | | A DIFFERENT ROOF SYSTEM PLEASE KEEP IN MIND TO REVIEW | | | THE NOTES ON THE PRODUCT APPROVAL - NOTE NUMBER 9 ON | | | THE PRODUCT APPROVAL - ADDITIONAL SIGNED AND SEALED | | | ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR | | | ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER PRESSURE | | | THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL. | | | | | | FYI - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO | | | BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR - | | | IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN | | | ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP OFF THE | | | ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE | | | FRONT DESK IN THE BUILDING DIVISION AT THE CITY HALL. | | | | | | |
|