| 2021-08-31 16:07:49 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21070963 |
| | |
| | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE. |
| | |
| | 1- NEW BEDROOM EGRESS WINDOWS DOESN'T SEEM TO COMPLY |
| | WITH SEC. R310.2.1 FBC-RESIDENTIAL. TYPICALLY, 5'-0" |
| | SINGLE HUNG IMPACT WINDOW DOESN'T PROVIDE THE REQUIRED |
| | 24" HEIGHT CLEARANCE. REVISE SIZE OF SINGLE HUNG WINDOW |
| | OR PROVIDE MANUFACTURER'S CUT SHEETS SHOWING THAT THE |
| | 5'-0" HIGH WINDOW PROVIDE THE REQUIRED. CLEAR HEIGHT. |
| | |
| | 2- EXISTING BEDROOM LOCATED ON SOUTH SIZE OF PROPOSED |
| | HALL. |
| | THIS BEDROOM USED TO HAVE AN EGRESS DOOR LEADING TO THE |
| | OUTSIDE. THE DOOR WAS REMOVED TO ALLOW FOR THE NEW |
| | ADDITION. SPECIFY SIZE AND TYPE OF EXISTING BEDROOM |
| | WINDOW TO REMAIN TO VERIFY COMPLIANCE WITH THE EGRESS |
| | REQUIREMENTS OF SEC. R310.2.1 FBC-RESIDENTIAL. |
| | |
| | 3- ADDITION IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT |
| | IS SPECIFYING R-30 CLOSED CELL SPRAYED INSULATION UNDER |
| | THE METAL ROOF. PROVIDE ICC EVALUATION REPORT FOR THE |
| | R-30 INSULATION IN THIS ROOFING SYSTEM TO VERIFY |
| | COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL. |
| | NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN |
| | WRITING PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | |
| | 4- ARCHITECT TO REVISE STUCCO THICKNESS SPECIFIED ON |
| | THE BUILDING SECTIONS. NEED TO SPECIFY THE 7/8" MIN. |
| | STUCCO THICKNESS AS REQUIRED BY TABLE R702.1(1). |
| | FBC-RESIDENTIAL. |
| | |
| | 5- ARCHITECT NEEDS TO SPECIFY TWO WATER RESISTIVE |
| | BARRIERS WHEN STUCCO IS APPLIED TO WOOD AS REQUIRED BY |
| | SEC. R703.7.3 FBC-RESIDENTIAL. |
| | |
| | 6- THERE IS A POOL IN THIS PROPERTY. PROVIDE |
| | SPECIFICATIONS SHOWING HOW THE ADDITION WILL COMPLY |
| | WITH THE RESIDENTIAL SWIMMING BARRIER REQUIREMENTS. |
| | SEC. R4501.17.1.9 FBC-RESIDENTIAL. |
| | |
| | 7- ENERGY CALCULATIONS SUBMITTED: |
| | A)THE ENERGY FORM R405-2020 IS REQUIRED TO BE SIGNED |
| | AND DATED BY THE OWNER, ARCHITECT OR OWNER?S LEGALLY |
| | DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS |
| | REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, |
| | PRIOR TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION. |
| | |
| | B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2 FBC- |
| | ENERGY CONSERVATION. |
| | |
| | C)REVISE ITEM #2 ON PAGE 1 OF 2. THE ANSWER IS |
| | INCORRECT. THE QUESTION IS IF THIS IS A SINGLE FAMILY |
| | OR MULTIPLE FAMILY? DETACHED |
| | IS NOT THE CORRECT ANSWER. REVISE AS REQUIRED. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | D)REVISE ITEM #11 ON PAGE 1 OF 4. ACCORDING TO PLANS. |
| | THE ATTIC IS NOT VENTED. SEE PLANS AND REVISE AS |
| | REQUIRED. ALSO, REVISE THE TYPE OF INSULATION ON PAGE 2 |
| | OF 4. IT IS FOAM INSULATION NOT BATT INSULATION. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | E)REVISE ROOF MATERIAL ON PAGE 2 OF 4. THERE ARE NO |
| | SHINGLES ON THIS ADDITION. IT IS METAL ROOFING. SEE |
| | PLANS AND REVISE AS REQUIRED. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | F)REVISE WINDOWS OVERHANG DEPTH AND SEPARATION ON PAGE |
| | 3 OF 4 TO MATCH PLANS. SEE PLANS AND REVISE AS |
| | REQUIRED. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | G) BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE |
| | LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| | CONSERVATION. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |