2021-08-13 17:46:4508/13/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET P-PB 03;
 A. THE FLOOR DRAIN THAT RECEIVES THE SUMP PUMP LOOKS TO
 BE OUTSIDE AND THAT LINE IS LABEL SANITARY SEWER LINE.
 STORM WATER SHALL NOT BE DRAINED INTO SEWERS INTENDED
 FOR SEWAGE ONLY PER THE 2020 FBC SEC. 1101.3 PROHIBITED
 DRAINAGE.
  
 B. IF THE FLOOR DRAIN IS GOING TO BE MOVED INSIDE IT
 WILL REQUIRE A TRAP PRIMER PER THE 2020 FBC SEC.
 1002.4.1 TRAP SEAL PROTECTION.
  
 C. PLEASE PROVIDE A PLUMBING ISOMETRIC RISER DIAGRAM
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13)
 COMMERCIAL PLUMBING.
  
 2. G-PB-103, UNDER APPLICABLE CODE IT STATES THE 6 TH
 EDITION PLEASE CORRECT TO THE 7 TH EDITION PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  