| 2021-08-13 17:46:45 | 08/13/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET P-PB 03; |
| | A. THE FLOOR DRAIN THAT RECEIVES THE SUMP PUMP LOOKS TO |
| | BE OUTSIDE AND THAT LINE IS LABEL SANITARY SEWER LINE. |
| | STORM WATER SHALL NOT BE DRAINED INTO SEWERS INTENDED |
| | FOR SEWAGE ONLY PER THE 2020 FBC SEC. 1101.3 PROHIBITED |
| | DRAINAGE. |
| | |
| | B. IF THE FLOOR DRAIN IS GOING TO BE MOVED INSIDE IT |
| | WILL REQUIRE A TRAP PRIMER PER THE 2020 FBC SEC. |
| | 1002.4.1 TRAP SEAL PROTECTION. |
| | |
| | C. PLEASE PROVIDE A PLUMBING ISOMETRIC RISER DIAGRAM |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13) |
| | COMMERCIAL PLUMBING. |
| | |
| | 2. G-PB-103, UNDER APPLICABLE CODE IT STATES THE 6 TH |
| | EDITION PLEASE CORRECT TO THE 7 TH EDITION PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |