| 2021-07-27 15:15:53 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THE STAIR DETAIL DID NOT INDICATE CLEARLY TEH DESIGN |
| | TO MINIMIZE WATER ACCUMULATION. |
| | |
| | PER NFPA 101 , CH 7 MEANS OF EGRESS |
| | |
| | 7.2.2.6.5* WATER ACCUMULATION. OUTSIDE STAIRS AND |
| | LANDINGS, OTHER |
| | THAN EXISTING OUTSIDE STAIRS AND LANDINGS, SHALL BE |
| | DESIGNED TO MINIMIZE |
| | WATER ACCUMULATION ON THEIR SURFACES. |
| | |
| | 7.2.2.3.4* TREAD AND LANDING SLOPE. THE TREAD AND |
| | LANDING SLOPE |
| | SHALL NOT EXCEED 1?4 IN./FT (21 MM/M) (A SLOPE OF 1 IN |
| | 48). |
| | |
| | A.7.2.2.3.4 A SMALL DRAINAGE SLOPE FOR STAIR TREADS |
| | SUBJECT TO WETTING |
| | CAN IMPROVE TREAD SLIP RESISTANCE (SEE ALSO |
| | A.7.2.2.3.3.2). A CONSISTENT |
| | SLOPE TO A SIDE OF THE STAIR, WHERE DRAINAGE IS |
| | POSSIBLE, MIGHT BE PREFERABLE |
| | TO A FRONT-TO-BACK SLOPE OF THE TREADS. PROVIDING A |
| | PITCH OF 1?8 IN./FT |
| | TO 1?4 IN./FT (10 MM/M TO 21 MM/M) AIDS THE SHEDDING OF |
| | WATER FROM A |
| | NOMINALLY HORIZONTAL SURFACE. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE. |
| | |
| | |
| | |
| | 2) THERE IS AN INDICATION OF A STEEL WIRE MESH |
| | SURROUNDING THE STAIRWAY/WALKWAY |
| | |
| | 7.2.2.6.6 OPENNESS. OUTSIDE STAIRS, OTHER THAN EXISTING |
| | OUTSIDE STAIRS, |
| | SHALL BE NOT LESS THAN 50 PERCENT OPEN ON ONE SIDE. |
| | OUTSIDE STAIRS SHALL |
| | BE ARRANGED TO RESTRICT THE ACCUMULATION OF SMOKE. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE |
| | |
| | |
| | |
| | 3) THERE WAS LIMITED INFORMATION REGARDING LIGHTING. |
| | |
| | 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| | PROVIDED IN ACCORDANCE |
| | WITH SECTION 7.8 FOR EVERY BUILDING AND STRUCTURE WHERE |
| | REQUIRED IN |
| | CHAPTERS 11 THROUGH 43. FOR THE PURPOSES OF THIS |
| | REQUIREMENT, EXIT ACCESS |
| | SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, |
| | CORRIDORS, RAMPS, ESCALATORS, |
| | AND PASSAGEWAYS LEADING TO AN EXIT. FOR THE PURPOSES OF |
| | THIS REQUIREMENT, |
| | EXIT DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, |
| | AISLES, CORRIDORS, |
| | RAMPS, ESCALATORS, WALKWAYS, AND PASSAGEWAYS LEADING TO |
| | A PUBLIC WAY |
| | |
| | 7.8.1.3 THE FLOORS AND OTHER WALKING SURFACES WITHIN AN |
| | EXIT AND WITHIN |
| | THE PORTIONS OF THE EXIT ACCESS AND EXIT DISCHARGE |
| | DESIGNATED IN 7.8.1.1 |
| | SHALL BE ILLUMINATED AS FOLLOWS: |
| | (1) DURING CONDITIONS OF STAIR USE, THE MINIMUM |
| | ILLUMINATION FOR NEW |
| | STAIRS SHALL BE AT LEAST 10 FT-CANDLE (108 LUX), |
| | MEASURED AT THE |
| | WALKING SURFACES. |
| | (2) THE MINIMUM ILLUMINATION FOR FLOORS AND OTHER |
| | WALKING SURFACES, |
| | OTHER THAN NEW STAIRS DURING CONDITIONS OF STAIR USE, |
| | SHALL BE TO |
| | VALUES OF AT LEAST 1 FT-CANDLE (10.8 LUX), MEASURED AT |
| | THE FLOOR. |
| | (3) IN ASSEMBLY OCCUPANCIES, THE ILLUMINATION OF THE |
| | WALKING SURFACES |
| | OF EXIT ACCESS SHALL BE AT LEAST 0.2 FT-CANDLE (2.2 |
| | LUX) DURING PERIODS |
| | OF PERFORMANCES OR PROJECTIONS INVOLVING DIRECTED |
| | LIGHT. |
| | (4)* THE MINIMUM ILLUMINATION REQUIREMENTS SHALL NOT |
| | APPLY WHERE |
| | OPERATIONS OR PROCESSES REQUIRE LOW LIGHTING LEVELS |
| | |
| | 7.8.2 SOURCES OF ILLUMINATION. |
| | 7.8.2.1 ILLUMINATION OF MEANS OF EGRESS SHALL BE FROM A |
| | SOURCE CONSIDERED |
| | RELIABLE BY THE AUTHORITY HAVING JURISDICTION. |
| | 7.8.2.2 BATTERY-OPERATED ELECTRIC LIGHTS AND OTHER |
| | TYPES OF PORTABLE LAMPS |
| | OR LANTERNS SHALL NOT BE USED FOR PRIMARY ILLUMINATION |
| | OF MEANS OF EGRESS. |
| | BATTERY-OPERATED ELECTRIC LIGHTS SHALL BE PERMITTED TO |
| | BE USED AS AN EMERGENCY |
| | SOURCE TO THE EXTENT PERMITTED UNDER SECTION 7.9. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE |
| | |
| | |
| | 4) THERE ARE NO INDICATIONS OF EXIT SIGNS |
| | |
| | 7.10.1.2 EXITS. |
| | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS |
| | THAT OBVIOUSLY |
| | AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED |
| | BY AN APPROVED |
| | SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT |
| | ACCESS. |
| | |
| | 7.10.1.2 EXITS. |
| | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS |
| | THAT OBVIOUSLY |
| | AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED |
| | BY AN APPROVED |
| | SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT |
| | ACCESS. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |