Plan Review Notes
Plan Review Notes For Permit 21070960
Permit Number 21070960
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-07-27 15:15:53THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE STAIR DETAIL DID NOT INDICATE CLEARLY TEH DESIGN
 TO MINIMIZE WATER ACCUMULATION.
  
 PER NFPA 101 , CH 7 MEANS OF EGRESS
  
 7.2.2.6.5* WATER ACCUMULATION. OUTSIDE STAIRS AND
 LANDINGS, OTHER
 THAN EXISTING OUTSIDE STAIRS AND LANDINGS, SHALL BE
 DESIGNED TO MINIMIZE
 WATER ACCUMULATION ON THEIR SURFACES.
  
 7.2.2.3.4* TREAD AND LANDING SLOPE. THE TREAD AND
 LANDING SLOPE
 SHALL NOT EXCEED 1?4 IN./FT (21 MM/M) (A SLOPE OF 1 IN
 48).
  
 A.7.2.2.3.4 A SMALL DRAINAGE SLOPE FOR STAIR TREADS
 SUBJECT TO WETTING
 CAN IMPROVE TREAD SLIP RESISTANCE (SEE ALSO
 A.7.2.2.3.3.2). A CONSISTENT
 SLOPE TO A SIDE OF THE STAIR, WHERE DRAINAGE IS
 POSSIBLE, MIGHT BE PREFERABLE
 TO A FRONT-TO-BACK SLOPE OF THE TREADS. PROVIDING A
 PITCH OF 1?8 IN./FT
 TO 1?4 IN./FT (10 MM/M TO 21 MM/M) AIDS THE SHEDDING OF
 WATER FROM A
 NOMINALLY HORIZONTAL SURFACE.
  
 PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE.
  
  
  
 2) THERE IS AN INDICATION OF A STEEL WIRE MESH
 SURROUNDING THE STAIRWAY/WALKWAY
  
 7.2.2.6.6 OPENNESS. OUTSIDE STAIRS, OTHER THAN EXISTING
 OUTSIDE STAIRS,
 SHALL BE NOT LESS THAN 50 PERCENT OPEN ON ONE SIDE.
 OUTSIDE STAIRS SHALL
 BE ARRANGED TO RESTRICT THE ACCUMULATION OF SMOKE.
  
 PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE
  
  
  
 3) THERE WAS LIMITED INFORMATION REGARDING LIGHTING.
  
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN ACCORDANCE
 WITH SECTION 7.8 FOR EVERY BUILDING AND STRUCTURE WHERE
 REQUIRED IN
 CHAPTERS 11 THROUGH 43. FOR THE PURPOSES OF THIS
 REQUIREMENT, EXIT ACCESS
 SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS,
 AND PASSAGEWAYS LEADING TO AN EXIT. FOR THE PURPOSES OF
 THIS REQUIREMENT,
 EXIT DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS,
 AISLES, CORRIDORS,
 RAMPS, ESCALATORS, WALKWAYS, AND PASSAGEWAYS LEADING TO
 A PUBLIC WAY
  
 7.8.1.3 THE FLOORS AND OTHER WALKING SURFACES WITHIN AN
 EXIT AND WITHIN
 THE PORTIONS OF THE EXIT ACCESS AND EXIT DISCHARGE
 DESIGNATED IN 7.8.1.1
 SHALL BE ILLUMINATED AS FOLLOWS:
 (1) DURING CONDITIONS OF STAIR USE, THE MINIMUM
 ILLUMINATION FOR NEW
 STAIRS SHALL BE AT LEAST 10 FT-CANDLE (108 LUX),
 MEASURED AT THE
 WALKING SURFACES.
 (2) THE MINIMUM ILLUMINATION FOR FLOORS AND OTHER
 WALKING SURFACES,
 OTHER THAN NEW STAIRS DURING CONDITIONS OF STAIR USE,
 SHALL BE TO
 VALUES OF AT LEAST 1 FT-CANDLE (10.8 LUX), MEASURED AT
 THE FLOOR.
 (3) IN ASSEMBLY OCCUPANCIES, THE ILLUMINATION OF THE
 WALKING SURFACES
 OF EXIT ACCESS SHALL BE AT LEAST 0.2 FT-CANDLE (2.2
 LUX) DURING PERIODS
 OF PERFORMANCES OR PROJECTIONS INVOLVING DIRECTED
 LIGHT.
 (4)* THE MINIMUM ILLUMINATION REQUIREMENTS SHALL NOT
 APPLY WHERE
 OPERATIONS OR PROCESSES REQUIRE LOW LIGHTING LEVELS
  
 7.8.2 SOURCES OF ILLUMINATION.
 7.8.2.1 ILLUMINATION OF MEANS OF EGRESS SHALL BE FROM A
 SOURCE CONSIDERED
 RELIABLE BY THE AUTHORITY HAVING JURISDICTION.
 7.8.2.2 BATTERY-OPERATED ELECTRIC LIGHTS AND OTHER
 TYPES OF PORTABLE LAMPS
 OR LANTERNS SHALL NOT BE USED FOR PRIMARY ILLUMINATION
 OF MEANS OF EGRESS.
 BATTERY-OPERATED ELECTRIC LIGHTS SHALL BE PERMITTED TO
 BE USED AS AN EMERGENCY
 SOURCE TO THE EXTENT PERMITTED UNDER SECTION 7.9.
  
 PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE
  
  
 4) THERE ARE NO INDICATIONS OF EXIT SIGNS
  
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS.
  
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS.
  
 PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL