| Plan Review Notes For Permit 21070953 |
| Permit Number |
21070953 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-07-27 06:08:25 | 1) SUBMIT MANUFACTURER'S SPECIFICATION SHEETSS FOR ALL | | | GAS APPLIANCES. GAS APPLIANCES SHALL BE LISTED AND | | | LABELED PER FBC-FUEL GAS SEC.301.3. | | | 2) THE REFERENCED TABLE ON THE PLANS FOR THE PE PIPE IS | | | FOR A 2 PSI SYSTEM YET THE PLANS SHOW A 12 INCH WATER | | | COLUMN. CLARIFY. | | | 3) SHOW THE DEVELOPED LENGTH OF THE SYSTEM FROM THE GAS | | | METER TO THE MOST REMOTE OUTLET ON THE SYSTEM. FBC-GAS | | | SEC.402.4. | | | 4) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THE GAS | | | APPLIANCES. THE DRYER MAY REQUIRE COMBUSTION AIR IF | | | LOCATED IN A ROOM WITH A DOOR. SUBMIT CALCULATIONS FOR | | | COMBUSTION AIR PER THE FBC-RES. SEC.G 2407.1 AND | | | G2439.4 (CLOTHES DRYERS). | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|