Plan Review Notes
Plan Review Notes For Permit 21070940
Permit Number 21070940
Review Stop B
Sequence Number 1
Notes
Date Text
2021-08-31 13:50:31ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW THE ROOF HEIGHT FBC WPB 107.2.1.1
 2) PLEASE SHOW THE ROOF SLOPE FOR THE TILE ROOF FBC WPB
 107.2.1.1
 3) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT
 APPROVAL FOR THE FLAT DECK REQUIRES ADDITIONAL SIGNED
 AND SEALED ATTACHMENT DETAILS FROM AN ARCHITECT OR
 ENGINEER FOR ROOF WIND ZONES 3 WHICH REQUIRES A HIGHER
 PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL
 (-105) - SEE NOTE 5.7.2 ON THE PRODUCT APPROVAL. FBC
 TABLE R301.2(2) SHOWS A WIND PRESSURE OF MORE THAN
 (-105) (NEED TO KNOW THE ROOF HEIGHT) EXPOSURE "C"
 SHOULD BE USED.