| Plan Review Notes For Permit 21070940 |
| Permit Number |
21070940 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-08-31 13:50:31 | ROOFING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - | | | 1) PLEASE SHOW THE ROOF HEIGHT FBC WPB 107.2.1.1 | | | 2) PLEASE SHOW THE ROOF SLOPE FOR THE TILE ROOF FBC WPB | | | 107.2.1.1 | | | 3) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT | | | APPROVAL FOR THE FLAT DECK REQUIRES ADDITIONAL SIGNED | | | AND SEALED ATTACHMENT DETAILS FROM AN ARCHITECT OR | | | ENGINEER FOR ROOF WIND ZONES 3 WHICH REQUIRES A HIGHER | | | PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL | | | (-105) - SEE NOTE 5.7.2 ON THE PRODUCT APPROVAL. FBC | | | TABLE R301.2(2) SHOWS A WIND PRESSURE OF MORE THAN | | | (-105) (NEED TO KNOW THE ROOF HEIGHT) EXPOSURE "C" | | | SHOULD BE USED. |
|