| | 21070936 255 EVERNIA ST 310 |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1.SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE A |
| | COMPLETE AND DETAILED SCOPE OF WORK. UPDATED FLOOR PLAN |
| | INDICATES BATHTUB REMOVAL IN GUEST BATH BUT IS UNCLEAR |
| | AS TO REPLACEMENT. CONVERSATION WITH OWNER AND GC |
| | INDICATES A SHOWER WILL BE PROVIDED. |
| | |
| | 2.SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE AN |
| | EXISTING FLOOR PLAN AND A PROPOSED FLOOR PLAN. CLEARLY |
| | INDICATE ANY CHANGES FROM THE EXISTING TO THE PROPOSED. |
| | |
| | 3. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE A |
| | DEDICATED PLUMBING FLOOR PLAN. THE PLUMBING PLAN IN |
| | ACCORDANCE WITH WPB FBC 107.3.4.3 SHALL BEAR THE |
| | PRINTED NAME, THE SIGNATURE AND THE CERTIFICATION |
| | NUMBER OF THE DESIGNER WHO SHALL BE A CONTRACTOR |
| | LICENSED IN THAT TRADE. |
| | PLEASE NOTE THAT WHEN SCANNED DRAWINGS ARE SUBMITTED |
| | WITH CONTRACTOR'S PRINTED NAME, SIGNATURE AND LICENSE |
| | NUMBER IN ACCORDANCE WITH WPB FBC 107.3.4.3, A PAPER |
| | PLAN WITH WET SIGNATURE SHALL BE PROVIDED TO THE |
| | BUILDING DEPARTMENT FOR HARD RECORD FILE PRIOR TO |
| | ISSUANCE OF A PERMIT. |
| | |
| | 4.PER WPB FBC 107.2.1, PROVIDE SHOWER PAN AND CURB |
| | DETAIL PROVIDING THE FOLLOWING REQUIREMENTS NOTED IN |
| | FBC PL 421.5.2. LINER SHALL TURN UP ON ALL SIDES NOT |
| | LESS THAN 2 INCHES (51 MM) ABOVE THE FINISHED THRESHOLD |
| | LEVEL. LINERS SHALL BE RECESSED AND FASTENED TO AN |
| | APPROVED BACKING SO AS NOT TO OCCUPY THE SPACE REQUIRED |
| | FOR WALL COVERING, AND SHALL NOT BE NAILED OR |
| | PERFORATED AT ANY POINT LESS THAN 1 INCH (25 MM) ABOVE |
| | THE FINISHED THRESHOLD. LINERS SHALL BE PITCHED |
| | ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL |
| | (2-PERCENT SLOPE) AND SHALL BE SLOPED TOWARD THE |
| | FIXTURE DRAINS AND BE SECURELY FASTENED TO THE WASTE |
| | OUTLET AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT |
| | JOINT BETWEEN THE LINER AND THE OUTLET. |
| | |
| | 5. PER WPB FBC 107.2.1, PROVIDE NOTE STATING ?PER FBC |
| | PL412.3, INDIVIDUAL SHOWER AND TUB-SHOWER COMBINATION |
| | VALVES SHALL BE BALANCED-PRESSURE, THERMOSTATIC OR |
| | COMBINATION BALANCED-PRESSURE/THERMOSTATIC VALVES THAT |
| | CONFORM TO THE REQUIREMENTS OF ASSE 1016/ASME |
| | A112.1016/CSA B125.16 OR ASME A112.18.1/CSA B125.1 AND |
| | SHALL BE INSTALLED AT THE POINT OF USE." |
| | |
| | 6.PER WPB FBC 107.2.1, PROVIDE UL ASSEMBLY FOR NEW |
| | SHOWER DRAIN PENETRATION. THIS SHALL INCLUDE |
| | REMEDIATION OF THE EXISTING TUB BOX. COMPLY WITH FBC |
| | CHAPTER 7. |
| | |
| | 7. PER WPB FBC 107.2.1, FAIR HOUSING ACT DESIGN MANUAL |
| | PAGE 7.52, PROVIDE NOTE ON PLANS THE CABINETS WILL BE A |
| | MAXIMUM 34 INCHES TO COMPLY WITH FHA DESIGN MANUAL PGE |
| | 7.52 |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |
| | 21070936 255 EVERNIA ST 310 |
| | |
| | |