| 2021-07-21 09:12:30 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. DESIGN CRITERIA IS SHOWN ON DEMO, CONSTRUCTION PLAN, |
| | POSSIBLY OTHER PAGES, AS FBC 2017 AND FBC 2010. |
| | GOVERNING CODE IS FBC 2020, REVISE. |
| | |
| | FOR ITEMS #2 AND #3 - ALTHOUGH I KNOW THAT TEST REPORTS |
| | ARE AVAILABLE FOR THE PROPOSED INSTALLATION, THE TEST |
| | REPORTS SHOULD BE SUBMITTED. PLEASE PROVIDE. |
| | |
| | 2. PROVIDE TEST REPORTS FOR THE FLOORING UNDERLAYMENT. |
| | THE UNDERLAYMENT MUST BE TESTED WITH WOOD GLUE DOWN |
| | FLOORING OR AN EQUIVALENCY ANALYSIS IS REQUIRED. |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| | CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | |
| | 3. REVISE PLAN TO SHOW FLOORIG PROPOSED IN BATHROOM. IF |
| | THIS IS NOT WOOD GLUE DOWN FLOORING, THE TEST REPORTS |
| | REFERENCED IN ITEM 2 ARE REQUIRED FOR TILE. |
| | |
| | |