| 2021-08-26 10:57:20 | 08/26/2 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF A |
| | PERMITTED GAS SYSTEM. IS THIS A NEW INSTALLATION? |
| | |
| | 2. WOULD YOU PLEASE SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE |
| | PER 2020 FBC FG SEC. 402.4.1, 402.4.2. |
| | |
| | 3. WOULD YOU PLEASE CLARIFY THE TYPE OF PIPE IN BLUE |
| | BEING USED FROM THE METER TO THE FIRST PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 4. WOULD YOU PLEASE SHOW THE DISTANCE FROM THE POINT OF |
| | THE DELIVERY GAS METER TO THE MOST REMOTE OUTLET IN THE |
| | BUILDING AND/OR SYSTEM PER THE 2020 FBC FG SEC. |
| | 402.4.1. |
| | |
| | 5. WOULD YOU PLEASE PROVIDE THE SIZING TABLE OR NOTE |
| | THE PLANS FOR THE BLUE PIPE PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 6. WOULD YOU PLEASE SUBMIT THE MANUFACTURERES |
| | SPECIFICATION SHEETS/INSTALLATION MANUAL FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC FG SEC. |
| | 305.1. |
| | |
| | 7. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020 |
| | FBC FG SECS. 402.2 AND 301.3. |
| | |
| | 8. WOULD YOU PLEASE SHOW AND LABEL ALL UNIONS IN FRONT |
| | OF REGULATOR 1 FOOT OF EITHER SIDE PER THE 2020 FBC FG |
| | SEC 410.2? |
| | |
| | 9. WOULD YOU PLEASE SHOW AND LABEL THE SHUT-OFF, AND |
| | THEY SHALL BE ACCESSIBLE WITHOUT MOVING THE EQUIPMENT |
| | PER THE 2020 FBC SEC. G2403 (202) GD, ACCESS. |
| | |
| | 10. WOULD YOU PLEASE SHOW AND LABEL ALL DRIP LEGS ON |
| | EQUIPMENT EXCEPT FOR APPLIANCES, RANGE, DRYERS & OD |
| | GRILLS PER THE 2020 FBC FG 408.2. |
| | |
| | 11. WOULD YOU PLEASE SUBMIT THE MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. |
| | SEC. G2421.1. |
| | |
| | 12. ALL THE BTU LOADS OF EACH APPLIANCE ARE SHOWN. |
| | WOULD YOU PLEASE TOTAL BTU LOAD ON THE SYSTEM AND |
| | DISPLAY IT ON PLANS PER THE 2020 FBC RES. SEC. G2413. |
| | |
| | 13. WOULD YOU PLEASE SUBMIT A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANK-LESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER AND ALL APPLIANCES? THE |
| | LOCATION OF THE WATER HEATER SHALL COMPLY WITH THE |
| | MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE |
| | PLAN CAN BE HAND-DRAWN PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |