2021-09-22 12:21:50ELECTRONIC SIGNATURE REVIEW
 PERMIT- 21070847
 9/22/21
  
 PLAN REVIEW RESULT: DENIED.
  
 1) THE WIND LOAD CALCULATIONS PREPARED BY THE ENGINEER
 HAVE BOTH COPIED DIGITAL AND PAPER SIGNATURES AND
 SEALS. CALCULATIONS PREPARED BY A FL. LICENSED ENGINEER
 THAT ARE TRANSMITTED ELECTRONICALLY SHALL BEAR THE
 DIGITAL SEAL SIGNATURE OF THE ENGINEER- FL. STATUTE
 471.025, AND SECTION 61G15-23.005 FAC.
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR
 ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND
 DOCUMENTS.
  
 A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL
 ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY
 CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION.
 THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE
 A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES
 NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.)
 YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE
 ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT
 USE A THIRD PARTY.
 YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT
 IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE
 AND DOCUMENT.
  
 AS AN ALTERNATIVE TO PROVIDING DIGITALLY SIGNED AND
 SEALED CALCULATIONS, SIGNED AND SEALED ENGINEERING IN
 PAPER FORM CAN BE BROUGHT INTO THE WPB BUILDING
 DEPARTMENT WITH A COMPLETED PLAN REVIEW REQUEST FORM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  