Plan Review Notes
Plan Review Notes For Permit 21070763
Permit Number 21070763
Review Stop E
Sequence Number 1
Notes
Date Text
2021-09-07 19:18:30ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RECEPTACLE SPACING NOT COMPLIANT WITH NEC 210.52.
 MORE RECEPTACLES REQUIRED INSIDE DWELLING.
  
 2. AFCI PROTECTION REQUIRED PER NEC 210.12A
  
 3. RECEPTACLE REQUIRED ON BOTH FRONT AND REAR OF
 DWELLING NEC 210.52E1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  