Text |
| 2022-03-08 12:46:28 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21070760 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THE |
| | CORRECT ADDRESS IN THE CITY OF WEST PALM BEACH AND |
| | USING THE CURRENT 2020 FBC EDITION. |
| | |
| | 2) PLEASE PROVIDE THE CURRENT 2020 FBC M 7TH EDITION ON |
| | THE MECHANICAL DRAWING. |
| | |
| | 3) PLEASE EXPLAIN THE LINE COMING FROM THE LARGE BLACK |
| | BOX ON THE MECHANICAL DRAWING THAT APPEARS TO BE GOING |
| | TO THE RETURN DUCT. THE BLACK BOX IS BEING SUPPLIED |
| | WITH A 10 INCH SUPPLY DUCT FROM THE AHU. THE DRAWING |
| | INDICATES THAT THE 12 INCH DUCT IS COMING FROM A SUPPLY |
| | DUCT AND WOULD NOT BE A RETURN DUCT BUT THE GRILLES ARE |
| | LABELED RETURN. FBC 107.2.1 |
| | |
| | 4) PLEASE REMOVE THE RETURN AIR GRILLE FROM THE KITCHEN |
| | AS YOU CANNOT TAKE RETURN AIR FROM A KITCHEN. FBC RES |
| | M1602.2-4 |
| | |
| | 5) PLEASE CLEARLY SHOW THE RETURN AIR DUCT AND THE |
| | SUPPLY AIR DUCT ARE SEPARATE AND DO NOT CONNECT. PLEASE |
| | ALSO SHOW A CLEAR RETURN AIR PATH FROM THE ROOMS WITH |
| | DOORS TO THE AHU AS THEY CURRENTLY SHOW EACH WITH A |
| | RETURN AIR GRILLE ATTACHED TO DUCT BUT NO RETURN FROM |
| | THIS DUCT IN THE OPEN AREA OF THE HOME TO LEAD BACK TO |
| | THE AHU. FBC RES M1602.2 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |