Plan Review Notes
Plan Review Notes For Permit 21070760
Permit Number 21070760
Review Stop M
Sequence Number 1
Notes
Date Text
2022-03-08 12:46:281ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21070760
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THE
 CORRECT ADDRESS IN THE CITY OF WEST PALM BEACH AND
 USING THE CURRENT 2020 FBC EDITION.
  
 2) PLEASE PROVIDE THE CURRENT 2020 FBC M 7TH EDITION ON
 THE MECHANICAL DRAWING.
  
 3) PLEASE EXPLAIN THE LINE COMING FROM THE LARGE BLACK
 BOX ON THE MECHANICAL DRAWING THAT APPEARS TO BE GOING
 TO THE RETURN DUCT. THE BLACK BOX IS BEING SUPPLIED
 WITH A 10 INCH SUPPLY DUCT FROM THE AHU. THE DRAWING
 INDICATES THAT THE 12 INCH DUCT IS COMING FROM A SUPPLY
 DUCT AND WOULD NOT BE A RETURN DUCT BUT THE GRILLES ARE
 LABELED RETURN. FBC 107.2.1
  
 4) PLEASE REMOVE THE RETURN AIR GRILLE FROM THE KITCHEN
 AS YOU CANNOT TAKE RETURN AIR FROM A KITCHEN. FBC RES
 M1602.2-4
  
 5) PLEASE CLEARLY SHOW THE RETURN AIR DUCT AND THE
 SUPPLY AIR DUCT ARE SEPARATE AND DO NOT CONNECT. PLEASE
 ALSO SHOW A CLEAR RETURN AIR PATH FROM THE ROOMS WITH
 DOORS TO THE AHU AS THEY CURRENTLY SHOW EACH WITH A
 RETURN AIR GRILLE ATTACHED TO DUCT BUT NO RETURN FROM
 THIS DUCT IN THE OPEN AREA OF THE HOME TO LEAD BACK TO
 THE AHU. FBC RES M1602.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  