| Plan Review Notes For Permit 21070718 |
| Permit Number |
21070718 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-07-21 11:01:02 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE NO INDICATIONS OF ELECTRICAL SERVICE | | | ACCESS, WIRE TYPE & SIZE, CONDUIT SIZE & TYPE, CONDUIT | | | ROUTING & ATTACHMENTS, ETC. | | | | | | PLEASE PROVIDE DETAILS. | | | | | | | | | 1A) THERE ARE NO INDICATIONS OF COMPLAINCE WITH ANY | | | NFPA INCLUDING BUT NOT LIMITED TO NFPA 70 AND NFPA 303 | | | | | | PER NFPA 303, FIRE PROTECTION STANDARD FOR MARINAS AND | | | BOATYARDS | | | | | | CHAPTER 5 ELECTRICAL WIRING AND EQUIPMENT | | | 5.1* NATIONAL ELECTRICAL CODE. THE REQUIREMENTS SET | | | FORTH | | | HEREIN SUPPLEMENT AND RELATE THE REQUIREMENTS OF NFPA | | | 70, | | | NATIONAL ELECTRICAL CODE, TO THE SPECIFIC CONDITIONS | | | AND COMBINATIONS | | | OF CONDITIONS FOUND IN MARINAS AND BOATYARDS AND SHALL | | | BE FOLLOWED IN ADDITION TO ANY REQUIREMENTS FOUND IN | | | NFPA70, | | | INCLUDING, BUT NOT LIMITED TO, ARTICLE 555. | | | | | | | | | PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT | | | AND COMPLIANCE | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|