| 2021-10-26 15:32:40 | RESIDENTIAL (R3) NEW ACCESSORY STRUCTURE, BUILDING |
| | AUDIT. |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21070716 |
| | |
| | 1- USE ACCESSORY STRUCTURE IS NOT CLEAR. SEC. 107.2.1 |
| | CITY AMENDMENTS. FLOOR PLANS SHOW AN ACCESSORY BUILDING |
| | FOR WORK SHOP AND STORAGE, WHILE SURVEY SHOWS A GARAGE |
| | BUILDING. ALL CONSTRUCTION PLANS NEED TO MATCH. |
| | NOTE: THERE IS ALSO, SOME CONFUSION BECAUSE ZONING IS |
| | APPROVING A GARAGE CONSTRUCTION NOT AN ACCESSORY |
| | STRUCTURE. SEE ZONING REVIEW STAMP ON SURVEY SUBMITTED. |
| | REVISE AS REQUIRED. |
| | |
| | 2- BUILDING DIMENSIONS SHOWN ON THE FLOOR PLAN AND |
| | BUILDING DIMENSIONS SHOWN ON THE SURVEY DON'T MATCH. |
| | SEC. 107.2.1 CITY AMENDMENTS. REVISE AS REQUIRED. |
| | |
| | 3- SHEET 3-3: ROOF SHEATHING INFORMATION IS NOT CLEAR. |
| | INFORMATION ON PLYWOOD ROOF SHEATHING NOTES A AND C, |
| | COMPONENTS AND CLADDING PRESSURE ZONES CHART AND NOTE |
| | ON THE RIGHT SIDE OF THE ROOF DIAGRAM DOESN'T MATCH. |
| | REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| | 61G20-3.001 FOR: |
| | A) WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE |
| | TO AVOID DELAYS/CONFLICTS). |
| | |
| | B)PEEL AND STICK SHINGLES UNDERLAYMENT SPECIFIED ON |
| | PLANS. |
| | |
| | 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 6- CLARIFY WHY SUBMITTING LINTEL NOA 20-0630.15 FOR |
| | 4",6" OR 12" LINTELS IF THIS TYPE OF LINTEL IS NOT |
| | SPECIFIED ON PLANS. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |