| 2022-01-24 16:22:23 | 3RD REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21070703 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THIS |
| | BUILDING. THE ENERGY CALCULATIONS SUBMITTED ARE FOR |
| | SINGLE FAMILY UNIT WITH 3 BEDROOMS AND A TOTAL |
| | CONDITIONED FLOOR AREA OF 2221. THE BUILDING IS A 2 |
| | UNIT APARTMENT BUILDING WITH A HOUSE LAUNDRY AND GYM |
| | AREA. THESE ENERGY CALCULATIONS SHOW 1 60 GAL. WATER |
| | HEATER BUT THE LATEST DRAWING SHOWS A GAS TANKLESS |
| | WATER HEATER. THESE ENERGY CALCULATIONS ALSO INDICATE 2 |
| | ZONES, BUT THERE ARE 3 HEATING SYSTEMS. FBC EC R403.7.1 |
| | |
| | 2) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS |
| | INDICATE ONLY 2 ZONES, BUT THERE ARE 3 MECHANICAL |
| | SYSTEMS: 1 FOR THE 1ST FLOOR APARTMENT, 1 FOR THE |
| | LAUNDRY ROOM, STORAGE AND GYM; AND 1 FOR THE 2ND FLOOR |
| | APARTMENT. PLEASE PROVIDE THE MECHANICAL EQUIPMENT |
| | SIZING CALCULATIONS TO REFLECT THIS. FBC EC R403.7.1 |
| | |
| | 3) WITH THE ADDITION OF THE NEW GAS WATER HEATER A GAS |
| | PERMIT WILL BE REQUIRED. |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |