| 2022-05-25 17:28:55 | 3RD REVIEW FBC-2020 RES. GAS |
| | PERMIT- 21070703 |
| | 5/25/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. CORRECTED GAS PLANS WERE |
| | JOT SUBMITTED FOR REVIEW. PLEASE SUBMIT CORRECT PLANS |
| | IN COMPLAINCE WITH THE COMMENTS BELOW. |
| | |
| | 1) THE GAS RISER IS INCOMPLETE. REFER TO FBC RES AND |
| | PROVIDE: |
| | |
| | A) TYPE AND SIZE OF RISER PIPES AT THE METER AND AT THE |
| | WATER HEATERS- SEC. G2413.1. |
| | |
| | B) LOCATIONS OF REGULATORS AND INLET AND OUTLET |
| | PRESSURES- SEC. G2421.1. |
| | |
| | C) TOTAL DEVELOPED LENGTH OF THE PIPING- SEC. |
| | G2413.4.1. |
| | |
| | D) ELECTRICAL BONDING OF PIPING THAT IS LIKELY TO |
| | BECOME ENERGIZED- SEC. G2411.1 |
| | |
| | 2) PROVIDE A PLAN VIEW SHOWING THE LOCATION OF THE |
| | WATER HEATERS AND REQUIRED CLEARANCE DISTANCES FROM |
| | GRADE, OVERHEAD CONSTRUCTION, AND OPENINGS AND AIR |
| | INTAKES INTO THE BUILDING- SEC.- G2427.8 & G2448.1 FBC |
| | RES. |
| | |
| | 3) THE RISER AND OTHER PLANS SHALL INCLUDE THE |
| | SIGNATURE OF THE LICENSED CONTRACTOR OR QUALIFIER |
| | RESPONSIBLE FOR THE DESIGN- SEC. 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |