| Plan Review Notes For Permit 21070703 |
| Permit Number |
21070703 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-09-28 14:10:59 | 2ND REVIEW FBC-2020 MECHANICAL | | | PERMIT-21070703 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A.1 SHOWS A RATED WALL BETWEEN THE APARTMENT | | | AND THE BUILDING COMMON AREA. THE MECHANICAL SYSTEM | | | CANNOT BE SHARED BETWEEN THE DWELLING UNIT AND THE | | | COMMON AREA AS THEY ARE 2 SEPARATE OCCUPANCIES. PLEASE | | | SHOW THAT EACH SPACE HAS IT?S OWN MECHANICAL SYSTEM. | | | FBC EC R403.1 | | | | | | 2) PLEASE PROVIDE NEW MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS FOR EACH APARTMENT AND THE COMMON AREA. | | | FBC EC R403.7.1 AND FBC EC C403.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|