2021-09-28 14:51:31ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) BRANCH CIRCUITS FROM BOTTOM UNIT PANEL "A" NOT
 ALLOWED TO FEED CIRCUITS IN GYM, STORAGE, LAUNDRY,
 OUTSIDE LIGHTS ECT. ECT. 210.25 NEED A SEPARATE PANEL
 AND MAIN.
  
 210.25 BRANCH CIRCUITS IN BUILDINGS WITH MORE THAN ONE
 OCCUPANCY.
 (A) DWELLING UNIT BRANCH CIRCUITS. BRANCH CIRCUITS IN
 EACH DWELLING UNIT SHALL SUPPLY ONLY LOADS WITHIN THAT
 DWELLING UNIT
 OR LOADS ASSOCIATED ONLY WITH THAT DWELLING UNIT.
 (B) COMMON AREA BRANCH CIRCUITS. BRANCH CIRCUITS
 INSTALLED FOR THE PURPOSE OF LIGHTING, CENTRAL ALARM,
 SIGNAL, COMMUNICATIONS,
 OR OTHER PURPOSES FOR PUBLIC OR COMMON AREAS OF A
 TWOFAMILY DWELLING, A MULTIFAMILY DWELLING, OR A
 MULTI-OCCUPANCY
 BUILDING SHALL NOT BE SUPPLIED FROM EQUIPMENT THAT
 SUPPLIES AN INDIVIDUAL DWELLING UNIT OR TENANT SPACE.