| Plan Review Notes For Permit 21070703 |
| Permit Number |
21070703 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-09-28 14:51:31 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) BRANCH CIRCUITS FROM BOTTOM UNIT PANEL "A" NOT | | | ALLOWED TO FEED CIRCUITS IN GYM, STORAGE, LAUNDRY, | | | OUTSIDE LIGHTS ECT. ECT. 210.25 NEED A SEPARATE PANEL | | | AND MAIN. | | | | | | 210.25 BRANCH CIRCUITS IN BUILDINGS WITH MORE THAN ONE | | | OCCUPANCY. | | | (A) DWELLING UNIT BRANCH CIRCUITS. BRANCH CIRCUITS IN | | | EACH DWELLING UNIT SHALL SUPPLY ONLY LOADS WITHIN THAT | | | DWELLING UNIT | | | OR LOADS ASSOCIATED ONLY WITH THAT DWELLING UNIT. | | | (B) COMMON AREA BRANCH CIRCUITS. BRANCH CIRCUITS | | | INSTALLED FOR THE PURPOSE OF LIGHTING, CENTRAL ALARM, | | | SIGNAL, COMMUNICATIONS, | | | OR OTHER PURPOSES FOR PUBLIC OR COMMON AREAS OF A | | | TWOFAMILY DWELLING, A MULTIFAMILY DWELLING, OR A | | | MULTI-OCCUPANCY | | | BUILDING SHALL NOT BE SUPPLIED FROM EQUIPMENT THAT | | | SUPPLIES AN INDIVIDUAL DWELLING UNIT OR TENANT SPACE. |
|