| Plan Review Notes For Permit 21070703 |
| Permit Number |
21070703 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-07-29 11:19:35 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21070703 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THIS IS 3 APARTMENTS WITH A COMMON GYM AND LAUNDRY | | | AREA. THERE SHOULD BE TENANT SEPARATION AND EACH UNIT | | | MUST HAVE ITS OWN MECHANICAL SYSTEM. PLEASE SUBMIT | | | MECHANICAL EQUIPMENT SIZING CALCULATIONS AND MECHANICAL | | | DRAWINGS SHOWING EACH UNIT HAVING IT?S OWN SYSTEM. THE | | | EQUIPMENT SIZING CALCULATIONS AND THE MECHANICAL SYSTEM | | | DESIGN MUST BE DIGITALLY SIGNED BY AN ENGINEER OR THE | | | MECHANICAL CONTRACTOR THAT HOLDS THE PERMIT TO INSTALL | | | THE SYSTEMS FOR THIS PROJECT. F.S. 471.003(H), NEITHER | | | SPACE CAN SHARE WITH THE OTHER. FBC M DEFINITIONS- | | | DWELLING UNIT. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|