| 2021-07-30 15:36:34 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SEVENTH EDITION (2020) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE DEMOLITION PLANS SHOW THAT THERE ARE 4 EXISTING |
| | APARTMENTS EACH WITH A KITCHEN AND AND A BATHROOM. THE |
| | OCCUPANCY TYPE FOR THIS BUILDING IS R-2. BECAUSE THIS |
| | IS NOT A ONE/ TWO FAMILY DWELLING OR A TOWNHOUSE THE |
| | FBC RESIDENTIAL CODE DOES NOT APPLY. THE CODES THAT DO |
| | APPLY ARE THE 2020 FBC EXISTING BUILDING AND FBC |
| | BUILDING. |
| | |
| | 2) THE PROPOSED FIRST FLOOR PLAN SHOWS ONE OF THE TWO |
| | UNITS WITH THE KITCHEN REMOVED AND BEING CONVERTED TO A |
| | GYM WITH A LAUNDRY ROOM AND A BEDROOM. PLEASE CLARIFY |
| | THE PURPOSE AND USE OF THIS AREA. FBC AMENDMENTS |
| | 107.2.1 |
| | |
| | 3) THE APARTMENTS ARE REQUIRED TO BE SEPARATED FROM |
| | EACH OTHER AND COMMON AREAS BY FIRE RESISTIVE RATED |
| | WALL PARTIONS AND FLOOR CEILING ASSEMBLIES. INDICATE |
| | THE RATED WALLS AND CEILINGS ON THE PLANS. FBC 420 |
| | |
| | 4) PROVIDE DETAILS THAT SHOW THE GUARDS AT THE |
| | BALCONIES AND STAIRS COMPLY WITH FBC 1015 FOR HEIGHT |
| | AND OPENING LIMITATIONS. |
| | |
| | 5) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE |
| | COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION ON |
| | THE SUBMITTED PLANS. ADDITIONAL PLAN REVIEW COMMENTS |
| | MAY BE GENERATED WHEN MORE INFORMATION IS PROVIDED. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |