2021-10-05 13:43:18THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO CLEAR INDICATION OF A REMOTE/ISOLATED
 EMERGENCY SHUTOFF OR LABLED DICONNECT SWITCH.
  
 IN COMPLIANCE OF NFPA 70, PLEASE REVIEW AND PROVIDE
 DETAILS OR THE PLAN SHEET # FOR IDENTIFCATION PURPOSES.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  