Plan Review Notes
Plan Review Notes For Permit 21070679
Permit Number 21070679
Review Stop E
Sequence Number 2
Notes
Date Text
2021-08-19 16:13:57ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E2.1.1
  
 1) LOUNGE NEED TO IDENTIFY OUTLETS THAT WILL BE GFCI
 PROTECTED PER 210.8(B)
  
 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL.
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL SHALL BE PROVIDED AS REQUIRED IN 210.8(A)
 THROUGH (E). THE
 GROUND-FAULT CIRCUIT INTERRUPTER SHALL BE INSTALLED IN
 A READILY ACCESSIBLE LOCATION.
  
 (B) OTHER THAN DWELLING UNITS. ALL SINGLE-PHASE
 RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 50
 AMPERES OR LESS AND THREEPHASE
 RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 100
 AMPERES OR LESS INSTALLED IN THE FOLLOWING LOCATIONS
 SHALL
 HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL. (5) SINKS ? WHERE RECEPTACLES ARE INSTALLED
 WITHIN 1.8 M
 (6 FT) FROM THE TOP INSIDE EDGE OF THE BOWL OF THE SINK
  
 2) CONFERENCE ROOM 100, ? AND BOARD ROOM WALL AND FLOOR
 OUTLETS TO MEET THE REQUIREMENTS OF 210.71
 210.71 MEETING ROOMS.
 (A) GENERAL. EACH MEETING ROOM OF NOT MORE THAN 93 M2
 (1000 FT2) IN OTHER THAN DWELLING UNITS SHALL HAVE
 OUTLETS FOR
 NONLOCKING-TYPE, 125-VOLT, 15- OR 20-AMPERE
 RECEPTACLES. THE OUTLETS SHALL BE INSTALLED IN
 ACCORDANCE WITH 210.71(B)(1)(2)
  
 (1) RECEPTACLE OUTLETS IN FIXED WALLS. RECEPTACLE
 OUTLETS SHALL
 BE INSTALLED IN ACCORDANCE WITH 210.52(A)(1) THROUGH
 (A)(4).
  
 (2) FLOOR RECEPTACLE OUTLETS. A MEETING ROOM THAT IS AT
 LEAST
 3.7 M (12 FT) WIDE AND THAT HAS A FLOOR AREA OF AT
 LEAST 20 M2
 (215 FT2) SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET
 LOCATED IN THE
 FLOOR AT A DISTANCE NOT LESS THAN 1.8 M (6 FT) FROM ANY
 FIXED WALL
 FOR EACH 20 M2 (215 FT2) OR MAJOR PORTION OF FLOOR
 SPACE
  
 3) PLEASE IDENTIFY THE OUTLETS THAT WILL BE TAMPER
 RESISTANT PER 406.12(B)(5)
  
 406.12 TAMPER-RESISTANT RECEPTACLES. ALL 15- AND
 20-AMPERE, 125- AND 250-VOLT NONLOCKING-TYPE
 RECEPTACLES IN THE AREAS
 SPECIFIED IN 406.12(1) THROUGH (7) SHALL BE LISTED
 TAMPERRESISTANT RECEPTACLES.
 (1) DWELLING UNITS IN ALL AREAS SPECIFIED IN 210.52 AND
 550.13
 (2) GUEST ROOMS AND GUEST SUITES OF HOTELS AND MOTELS
 (3) CHILD CARE FACILITIES
 (4) PRESCHOOLS AND ELEMENTARY EDUCATION FACILITIES
 (5) BUSINESS OFFICES, CORRIDORS, WAITING ROOMS AND THE
 LIKE IN
 CLINICS, MEDICAL AND DENTAL OFFICES AND OUTPATIENT
 FACILITIES
 (6) SUBSET OF ASSEMBLY OCCUPANCIES DESCRIBED IN 518.2
 TO
 INCLUDE PLACES OF WAITING TRANSPORTATION, GYMNASIUMS,
 SKATING RINKS, AND AUDITORIUMS
 (7) DORMITORIE
  