| 2021-08-19 16:13:57 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | PAGE E2.1.1 |
| | |
| | 1) LOUNGE NEED TO IDENTIFY OUTLETS THAT WILL BE GFCI |
| | PROTECTED PER 210.8(B) |
| | |
| | 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR |
| | PERSONNEL. |
| | GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR |
| | PERSONNEL SHALL BE PROVIDED AS REQUIRED IN 210.8(A) |
| | THROUGH (E). THE |
| | GROUND-FAULT CIRCUIT INTERRUPTER SHALL BE INSTALLED IN |
| | A READILY ACCESSIBLE LOCATION. |
| | |
| | (B) OTHER THAN DWELLING UNITS. ALL SINGLE-PHASE |
| | RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 50 |
| | AMPERES OR LESS AND THREEPHASE |
| | RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 100 |
| | AMPERES OR LESS INSTALLED IN THE FOLLOWING LOCATIONS |
| | SHALL |
| | HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR |
| | PERSONNEL. (5) SINKS ? WHERE RECEPTACLES ARE INSTALLED |
| | WITHIN 1.8 M |
| | (6 FT) FROM THE TOP INSIDE EDGE OF THE BOWL OF THE SINK |
| | |
| | 2) CONFERENCE ROOM 100, ? AND BOARD ROOM WALL AND FLOOR |
| | OUTLETS TO MEET THE REQUIREMENTS OF 210.71 |
| | 210.71 MEETING ROOMS. |
| | (A) GENERAL. EACH MEETING ROOM OF NOT MORE THAN 93 M2 |
| | (1000 FT2) IN OTHER THAN DWELLING UNITS SHALL HAVE |
| | OUTLETS FOR |
| | NONLOCKING-TYPE, 125-VOLT, 15- OR 20-AMPERE |
| | RECEPTACLES. THE OUTLETS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH 210.71(B)(1)(2) |
| | |
| | (1) RECEPTACLE OUTLETS IN FIXED WALLS. RECEPTACLE |
| | OUTLETS SHALL |
| | BE INSTALLED IN ACCORDANCE WITH 210.52(A)(1) THROUGH |
| | (A)(4). |
| | |
| | (2) FLOOR RECEPTACLE OUTLETS. A MEETING ROOM THAT IS AT |
| | LEAST |
| | 3.7 M (12 FT) WIDE AND THAT HAS A FLOOR AREA OF AT |
| | LEAST 20 M2 |
| | (215 FT2) SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET |
| | LOCATED IN THE |
| | FLOOR AT A DISTANCE NOT LESS THAN 1.8 M (6 FT) FROM ANY |
| | FIXED WALL |
| | FOR EACH 20 M2 (215 FT2) OR MAJOR PORTION OF FLOOR |
| | SPACE |
| | |
| | 3) PLEASE IDENTIFY THE OUTLETS THAT WILL BE TAMPER |
| | RESISTANT PER 406.12(B)(5) |
| | |
| | 406.12 TAMPER-RESISTANT RECEPTACLES. ALL 15- AND |
| | 20-AMPERE, 125- AND 250-VOLT NONLOCKING-TYPE |
| | RECEPTACLES IN THE AREAS |
| | SPECIFIED IN 406.12(1) THROUGH (7) SHALL BE LISTED |
| | TAMPERRESISTANT RECEPTACLES. |
| | (1) DWELLING UNITS IN ALL AREAS SPECIFIED IN 210.52 AND |
| | 550.13 |
| | (2) GUEST ROOMS AND GUEST SUITES OF HOTELS AND MOTELS |
| | (3) CHILD CARE FACILITIES |
| | (4) PRESCHOOLS AND ELEMENTARY EDUCATION FACILITIES |
| | (5) BUSINESS OFFICES, CORRIDORS, WAITING ROOMS AND THE |
| | LIKE IN |
| | CLINICS, MEDICAL AND DENTAL OFFICES AND OUTPATIENT |
| | FACILITIES |
| | (6) SUBSET OF ASSEMBLY OCCUPANCIES DESCRIBED IN 518.2 |
| | TO |
| | INCLUDE PLACES OF WAITING TRANSPORTATION, GYMNASIUMS, |
| | SKATING RINKS, AND AUDITORIUMS |
| | (7) DORMITORIE |
| | |