2021-09-07 08:39:2509/07/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET A9.0.1;
  
 A. ON DETAIL 9, WOULD YOU PLEASE SHOW THE CLEAR FLOOR
 SPACE UNDER THE DRINKING FOUNTAIN OF 27 INCHES OF KNEE
 CLEARANCE PER THE 2020 FBC SEC. 306.3 KNEE CLEARANCE.
  
 B. WOULD YOU PLEASE ADD THE MIRROR'S REFLECTIVE PART TO
 THE OF 40 INCHES TO THE REFLECTIVE SIDE PER THE 2020
 FBC ACC SEC. 603.3.
  
 C. THE TOILET GRAB BAR SAYS 6 INCHES FROM THE WALL,
 WHICH IS NOT AN ACTUAL NUMBER AS THE TOILET IS 16
 INCHES TO 18 INCHES TO THE CENTER, AND THAT NUMBER MAY
 CONFUSE THE INSTALLER. WOULD YOU PLEASE CORRECT PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 D. WOULD YOU, PLEASE SHOW THE FLUSH CONTROL TO BE 36
 INCHES MAXIMUM ABOVE THE FINISH FLOOR PER THE 2020 FBC
 ACC SEC. 604.9.5.
  
 E. ON DETAIL A, WOULD YOU PLEASE PROVIDE THE DIMENSION
 FOR THE CLEAR FLOOR SPACE FOR THE WATER CLOSET AND LAV
 PER THE 2020 FBC ACCESSIBILITY CODE.
  
 F. DETAIL 3 AND 7 SHOW THE FLUSH CONTROL, NOT THE OPEN
 SPACE PER THE 2020 FBC SEC. 604.6 FLUSH CONTROLS.
  
 2. ON SHEET A9.0.2;
  
 A. ON DETAIL 1, WOULD YOU PLEASE PROVIDE THE DIMENSION
 FOR THE CLEAR FLOOR SPACE FOR THE WATER CLOSET AND LAV
 PER THE 2020 FBC ACCESSIBILITY CODE.
  
 B. ON THAT SAME DETAIL, WOULD YOU PLEASE PROVIDE THE
 CLEAR FLOOR SPACE AND DIMENSION FOR THE LAV IN THE OPEN
 AREA OF 30 INCHES X 48 INCHES PER THE 2020 FBC SEC. ACC
 305.3.
  
 C. ON DETAIL 2, THE LAV ACCESSIBLE ON THE OPEN AREA,
 WOULD YOU PLEASE SHOW THE MIRROR'S REFLECTIVE PART TO
 THE OF 40 INCHES TO THE REFLECTIVE SIDE PER THE 2020
 FBC ACC SEC. 603.3.
  
 D. ON DETAIL 6, IT HAS THE HANDLE ON THE OPEN SIDE PER
 THE 2020 FBC ACC SEC. 604.9.5.
  
 E. THERE IS A DRINKING FOUNTAIN AND NO DETAIL FOR
 ACCESSIBILITY WITH ITS DEMISSION AND THE HEIGHT EITHER.
 WOULD YOU PLEASE PROVIDE PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. ON SHEET A9.0.2;
  
 A. ON DETAIL 1, WOULD YOU PLEASE PROVIDE THE DIMENSION
 FOR THE CLEAR FLOOR SPACE FOR THE WATER CLOSET AND LAVS
 AND URINAL PER THE 2020 FBC ACCESSIBILITY CODE.
  
 B. ON DETAIL 5, THE REFLECTIVE PART OF THE MIRROR NEEDS
 TO BE 40 INCHES TO THE REFLECTIVE SIDE PER THE 2020 FBC
 ACC SEC. 603.3.
  
 C. ON DETAIL 6, IT HAS THE HANDLE ON THE OPEN SIDE PER
 THE 2020 FBC ACC SEC. 604.9.5.
  
 D. ON THAT SAME DETAIL, WOULD YOU PLEASE PROVIDE THE
 CLEAR FLOOR SPACE AND DIMENSION FOR THE LAV IN THE OPEN
 AREA OF 30 INCHES X 48 INCHES PER THE 2020 FBC SEC. ACC
 305.3.
  
 E. WOULD YOU PLEASE SHOW THE DIMENSION FOR THE URINAL
 OF A MINIMUM OF 30 INCHES PER THE 2020 FBC SEC. P
 405.3.1.
  
 4. ON SHEET P6.0.1;
  
 A. ICEMAKER AND COFFEE MAKER SHALL BE EQUIPPED WITH AN
 IN-LINE VACUUM BREAKER THAT COMPLIES WITH ASSE 1024 PER
 THE 2020 FBC SEC. 608.13.10.
  
 B. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. WOULD YOU PLEASE MAKE A NOTE ON THIS SHEET?
  
 5. ON SHEET P7.0.2;
  
 A. ON THE ROOF, THERE IS A HOSE BIBB THAT REQUIRES A
 SHUT-OFF VALVE PER THE 2020 606.2 (2) LOCATION OF
 SHUTOFF VALVES.
  
 B. THE RECIRCULATING MANIFOLD TO THE HOT WATER LINES
 SHALL BE SUPPLIED TO THE SOURCE; PLEASE REFER TO THE
 2020 FBC ENERGY CODE TABLE C404.5.1. MAXIMUM ALLOWABLE
 PIPE LENGTH METHOD.
  
 C. HOT WATER LINES ARE LOOPED FOR THE RECIRCULATING
 SYSTEM, AND IT IS NOT IN A CONTINUOUS LOOP. THERE IS A
 REQUIREMENT IN THE FLORIDA ENERGY CODE SEC. C404.6.1.
 THERE IS A TABLE THAT LIMITS THE BETWEEN THE SOURCE AND
 THE OUTLET. PLEASE REFER TO TABLE 405.5.1 FOR THE
 MAXIMUM ALLOWABLE PIPE LENGTH METHOD AND SIZE
 ACCORDANTLY.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, DESCRIBING THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  